{| | {| border="1" class="wikitable" style="text-align:center" | ||
! | !Starting address || Quantity || Purpose || In modifications | ||
! | !From firmware version | ||
|- | |- | ||
| 0 || 1 || style="text-align:left" | | | 0 || 1 || style="text-align:left" |Enable buzzer (buzzer) || WB-MSW2, WB-v MSW.3 | ||
| | | | ||
|- | |- | ||
| 1 || 1 || style="text-align:left" | | | 1 || 1 || style="text-align:left" | Forced calibration of the built-in CO2 sensor. Turn on after 20 minutes of operation at a CO2 level of 400 ppm || WB-MSW2 | ||
| | | | ||
|- | |- | ||
| 2 || 1 || style="text-align:left" | | | 2 || 1 || style="text-align:left" | Turn on the heating (heater) in the temperature and humidity sensor chip HDC1080 || WB-MS (in the 2017 series), WB-MSW2, WB-MSW V. 3 | ||
|3.2.0 | |3.2.0 | ||
|- | |- | ||
|3 | |3 | ||
|1 | |1 | ||
| | |The inclusion of a CO2 sensor | ||
|WB-MSW | |WB-MSW V. 3 | ||
|4.1.0 | |4.1.0 | ||
|- | |- | ||
| 10 || 1 || style="text-align:left" | | | 10 || 1 || style="text-align:left" | Green led on || WB-MSW V. 3 | ||
| | | | ||
|- | |- | ||
| 11 || 1 || style="text-align:left" | | | 11 || 1 || style="text-align:left" | Enable red led || WB-v MSW.3 | ||
| | | | ||
|- | |- |