14 digital dry contact inputs module (WBIO-DI-DR-14)

Материал из Wiren Board
Это утверждённая версия страницы. Она же — наиболее свежая версия.
Другие языки:

Внимание: Отображаемое название «14 digital dry contact inputs module (WBIO-DI-DR-14)» переопределяет ранее заданное отображаемое название «WBIO-DI-DR-14 I/O Module». The model is discontinued. Recommended replacement is WBIO-DI-WD-14

Buy WBIO-DI-WD-14 online

WBIO-DI-DR-14 mmodule

Purpose

Connection of pulse counters, buttons, switches, sensors with dry contact output.

Technical specifications

It contains 14 inputs for connection of dry contacts, which are united in two groups of 7 inputs with group galvanic isolation. The scheme of inputs is shown in the figure. The terminal is supplied with ~ 4.5 V, when the small (1 mA) current is supplied to the ground, causing the operation of the input.

Parameter Value
Number of inputs 14
Isolated input groups 2
Input type dry contact,

the opening by the current at

circuit to the ground

Operation condition GND input lockout circuit
Tripping current 1 mA
Minimum pulse width to trigger 10 MS
Minimum time between consecutive signals 5 MS
Voltage "wetting" 4.5 V
Module type "I" (inverted address scheme)
Maximum power consumption 0.1 W
Width, DIN units 2
Size 36,3x90,2x57,5 mm
Terminals and wire section
The recommended wire cross section with pin bushing insulated tip, mm2 0,75 — 1
Standard sleeve length of pin bushing insulated tip, mm 8
Tightening torque of screws, Н∙м 0,2
Dimensions

Connection to controller

See activating the module in the web interface of the controller.

Connection

Sensors/counters with pulse outputs/buttons.

Such devices form a signal by closing two wires that are suitable for them. Connect one wire to the GND terminal of the module. Connect the second wire to the Dx terminal. Some counters have a pulse output on the optocoupler, then the two wires have a polarity - "plus" and "minus". In this case, minus is connected to GND, plus to Dx.

Devices with open collector output.

Both device and controller must be connected to the common grounding bus. Connect the open collector output to the Dx terminal.

The module inputs are galvanically isolated from the controller. Therefore, the ground GND of the module and the controller may be different.

Digital inputs DI


Images and drawings of the device