Discrete inputs dry contact module (WBIO-DI-DR-8)

From Wiren Board
This is the approved revision of this page, as well as being the most recent.

Внимание: Отображаемое название «Discrete inputs dry contact module (WBIO-DI-DR-8)» переопределяет ранее заданное отображаемое название «WBIO-DI-DR-8 I/O Module».

WBIO-DI-DR-8 Module

This model is discontinued​. WBIO-DI-WD-14 is a recommended replacement. Buy WBIO-DI-WD-14 online

Applicability

Connection of pulse counters, buttons, switches, sensors with dry contact output.

Technical specifications

Contains 8 dry contacts inputs with group galvanic isolation. The scheme of inputs is shown in the figure. The terminal is supplied by ~ 4.5 V voltage, when the ground fault,flows a small (1mA) current, causing the operation of the input.

Parameter Value
Number of inputs 8
Isolated input groups 1
Input type dry contact,

the opening by the current at

ground fault

Operation condition GND input lockout
Tripping current 1 mA
Minimum pulse width to trigger 10 MS
Minimum time between consecutive signals 5 MS
Voltage of "wetting" 4.5 V
Module type "I" (inverted address scheme)
Maximum power consumption 0.1 W
Width, DIN units 2
Size 36,3x90,2x57,5 mm
"'Terminals and wire section'"
Recommended wire cross-section with TSVI, mm2 0,75 — 1
Length of the standard sleeve NSVE, mm 8 (10 for adjusting screwless terminal blocks)
Torque of screws, N∙m 0,2 (for screw terminals)


Dimensions

Connection to the controller

See Activating the modules in the web interface of the controller

Connection

Sensors/counters with pulse outputs/buttons.

Such devices form a signal by closing two wires that are suitable for them. Connect one wire to the GND terminal of the module. Connect the second wire to the Dx terminal. Some counters have a pulse output on the optocoupler, then the two wires have a polarity - "plus" and "minus". In this case, minus is connected to GND, plus - to Dx.

Devices with open collector output.

Both device and controller must be connected to the common grounding bus. Connect the "open collector" output to the Dx terminal.

The module inputs are galvanically isolated from the controller. Therefore, the ground GND of the module and the controller may be different.

Digital inputs DI

Images and drawings of the device


По ссылкам ниже вы можете скачать изображения и чертежи устройства WBIO-DI-DR-8.

Corel Draw 2018: WBIO-DI-DR-8.cdr.zip

Corel Draw PDF: WBIO-DI-DR-8.cdr.pdf

Autocad 2013 DXF: WBIO-DI-DR-8.dxf.zip

Autocad PDF: WBIO-DI-DR-8.pdf