WBMZ-BATTERY - backup power module with a Li-Ion battery

Материал из Wiren Board
Это утверждённая версия страницы. Она же — наиболее свежая версия.
Другие языки:

Additional mezzanine board is installed on the second level in the DIN-rail mounted controller body.

Top view
Backup power module with LIR103450A battery
Mounting the module

Compatible withWiren Board 5 controller. It is connected by a loop to the internal connector of the controller.

The Board contains a charge circuit Li-Ion battery with charge protection at low and high temperatures.

There is no protection against over-discharge of the connected accmulator - be sure to use batteries with built-in protection circuit.

The boards are equipped with 1800 mAh batteries.

The controller receives two signals:

  • STAT1 (active low) - the board is connected.
  • STAT2 (active low) - the battery is charging.

Charging current is set by sealed jumpers:

  • not soldered - 300 мA.
  • one sealed - 600 ма.
  • two sealed - 900 ма.

The standard versions:

Package Contents Capacity Weight
WBMZ-BATTERY-1800MAH Module with LIR103450A-PCB-LD battery 1800 mAh 50 g


=== Technical characteristics of the LIR103450A batteries

===
Type Li-ion
Rated voltage 3,7 В
Rated capacity (C) 1800 мАч
Maximum charge/discharge 1 C
Charging time 0,5 C — 5 hours

1 C — 2,5 hours;

charging voltage 4,2 V
Operating temperature Charge: 0°C to 45°C

Discharge: -20°C to 55°C

Storage temperature
Charge/discharge cycles 300


Connecting the module that comes with the controller

Switch on the top cover of the controller

If the battery module is supplied with the controller, its connection will require minimal effort. Controllers with a battery module inside are equipped with a cover with a switch. The module itself is disconnected from the controller to avoid battery discharge. To connect the module, the cover with the switch is carefully removed with a screwdriver inserted into the side slots between the cover and the top of the housing. The switch must be connected to the connector on the controller Board. Next, you need to connect to the module loop connecting it to the board, as shown in the figures.

Initially, the loop connector is not connected to the module
Insert the plug of the loop
And push inside the connector until it stops

Replace the top cover of the controller. The controller is ready for operation.

=Connecting a module purchased separately =

Battery module, one battery contact disconnected
The top cover of the controller enclosure with a switch
The jumpers under the top cover can be removed
Controller board with battery and switch connectors


Disassemble the controller body according to the instructions .

The WBMZ battery module comes complete with the top cover of the case on which the switch is mounted. The cover is installed instead of the included controller. The old cover is removed with a screwdriver inserted into the side slots between the cover and the top of the housing.

One battery contact is disconnected from the module to prevent discharge during storage. Before installation it is necessary to fix the disconnected contact in a screw clip of the module (it is shown in drawing by arrows).

For the convenience of installing the jumper module in the upper part of the body can be removed (for example, wire cutters).


Module mounting

The module Board is mounted on two latches (indicated in the figure), the battery down to the side of the Board. The battery should be located on the side of the side power module opening (shown by arrow). Do not apply pressure to the battery during installation — this may cause an internal short circuit and fire!

After installing the module, connect the connectors to the Board, as shown by the arrows in the figure "controller Board with battery and switch connectors": red arrow — switch connector, blue — module connector.

When assembling the controller with the module installed, pay attention to the wires of the module: they should not be between the indicator and the plastic light guide of the upper cover of the controller body. Removal of the module is made in the reverse order.