WBIO-DI-LVD-8 voltage presence module

Материал из Wiren Board
Это утверждённая версия страницы. Она же — наиболее свежая версия.
Другие языки:

The model is discontinued. Recommended replacement is WBIO-DI-WD-14

Buy WBIO-DI-WD-14 online

WBIO-DI-LVD-8

Purpose

Input of discrete signals, control of circuit integrity, etc.

Technical specifications

Contains 8 inputs to determine the presence of voltage, both alternating (50Hz) and constant voltage of both polarities.

Parameter Value
Number of inputs 8
Isolated input groups 2: [1 — 4] and [5 — 8]
Input type voltage input
Operating voltage
  • detecting signal — >9V AC/DC
  • no signal <5 V AC/DC
Rated voltage 12 — 24 V AC/DC
Maximum permissible voltage 50 V AC/DC
Response time, not more than 100 MS
Isolation voltage between input and controller 5000 V (RMS.)
Module type I (inverted addr.)
Maximum power consumption 1 mW
Width, DIN units 2
Size 36.3 x 90.2 x 57.5 mm


Terminals and wire section
The recommended wire cross section with pin bushing insulated tip, mm2 2,5
Standard sleeve length of pin bushing insulated tip, mm 8
Tightening torque of screws, Н∙м 0,5
Dimensions

Connection to controller

See section activating the module in the web interface of the controller.

Connection

The voltage is applied to the COM terminal block and the corresponding module input. The inputs are separated by two isolated terminal groups: (1,2,3,4,COM,COM) and (COM, COM,5,6,7,8). Com terminals are common to a group of inputs.

Wbio-DI-LVD-8 Pinout
WBIO-DI-LVD module wiring diagram

Device pictures and drawings


По ссылкам ниже вы можете скачать изображения и чертежи устройства WBIO-DI-LVD-8.

Corel Draw 2018: WBIO-DI-LVD-8.cdr.zip

Corel Draw PDF: WBIO-DI-LVD-8.cdr.pdf

Autocad 2013 DXF: Мы еще не подготовили чертеж этого устройства. Вы можете запросить чертеж устройства "WBIO-DI-LVD-8 mo" на портале техподдержки Wiren Board (необходима регистрация).