WB-MCM16 pulse counter module with Modbus RTU

Материал из Wiren Board
Это утверждённая версия страницы. Она же — наиболее свежая версия.
Другие языки:
WB-MCM16 module
WB-MCM16 Module
WB-MCM16 Module
WB-MCM16 Module, push terminals

The model is discontinued. Recommended replacement - WB-MCM8. Buy WB-MCM8 in the online store


Purpose

The module of discrete and counting inputs 16-channel WB-MCM16 is designed to connect signals of dry contact and open collector, connection of metering devices of water, electricity, gas, etc. with pulse outputs.

No pre-configuration of input modes is required. There is protection against overfilling of the pulse counter.

Version: housing on DIN-rail (width 3 units). Supply voltage 12 – 24V

The module is controlled from the controller or PC via the RS-485 bus by MODBUS commands, as well as by external buttons.

Technical specifications

  • 16 digital inputs with pulse counting support with built-in voltage sources
  • Minimum pulse duration: 21ms, maximum pulse frequency: 25 Hz
  • Group galvanic isolation of inputs from RS-485 interface, up to 1.5 kV.
  • Supply voltage: 11 to 24 V.
  • Power consumption: 0.3 W.
  • Interface: RS485, Modbus RTU.
  • Save counter values when power is off
  • Led indication for power and data exchange
  • Install in the electrical panel on a DIN rail, housing width 3 DIN.


Terminals and wire section
Recommended wire cross-section with TSVI, mm2 0,75 — 1
Length of the standard sleeve NSVE, mm 8 (10 for adjusting screwless terminal blocks)
Torque of screws, N∙m 0,2 (for screw terminals)

Operating conditions

  • Air temperature from -40°C to +50°C;
  • Relative humidity up to 92%,without moisture condensation.

Connection

The module is made in a plastic case and is designed for installation in a mounting box on a DIN rail. The scheme of inputs is shown in the figure. The terminal is supplied ~ 4.5 V, when the earth current flows a small (1.5 mA), causing the operation of the input.

Digital inputs

To be done...

Management

See Modbus protocol

Bus parameters.

Speed 9600 bit/s, data - 8 bit, parity – no, stop bit - 2.


Modbus commands supported by the device

Command command (dec)
READ_DISCRETE_INPUTS 2
READ_HOLDING_REGISTERS 4
READ_HOLDING_REGISTERS 3
WRITE_SINGLE_REGISTER 6
WRITE_MULTI_REGISTERS 16

Address change is broadcast (slave_id 0) team record (WRITE_SINGLE_REGISTER) to holding register with address 128 (0x80).

The address 200 has a 6-byte signature. The signature is unique for each device model and allows you to identify the model. To obtain the signatures necessary to fulfill READ_HOLDING_REGISTERS address 200 length 6. Writing to this area of memory is not supported and error 3 is returned when attempting to write to an invalid location.


Register map

Регистр / адрес (dec) тип чтение/запись формат назначение
0 discrete input R 1 or 0 состояние входа #1
...
15 discrete input R 1 or 0 состояние входа #16
20 - 23 input/holding R 64-битное целое без знака. Big-endian порядок байт. 4 регистра на канал счетчик импульсов на входе #1.
...
80 - 83 input/holding R 64-битное целое без знака. Big-endian порядок байт. 4 регистра на канал счетчик импульсов на входе #16.
100 holding RW регистр сброса. Запись 1 в регистр приводит к сбросу всех счётчиков на всех каналах
200-206 input/holding R {'W','B','C',M','1','6'} сигнатура
220-243 input/holding R __date__ __time__ дата сборки прошивки
128 holding W 1-247 адрес Modbus

Назад к списку периферийных устройств


Изображения и чертежи устройства


По ссылкам ниже вы можете скачать изображения и чертежи устройства WB-MCM16.

Corel Draw 2018: WB-MCM16.cdr.zip

Corel Draw PDF: WB-MCM16.cdr.pdf

Autocad 2013 DXF: WB-MCM16.dxf.zip

Autocad PDF: WB-MCM16.pdf