Depending on the value written to the storage register 0x06, after the power is turned off and restored, the relays will remain off (if the value is 0, or turn on those that were turned on before the power interruption if the register has a value of 1). This feature appeared in the modules with the firmware, starting with version 1.5.3. | Depending on the value written to the storage register 0x06, after the power is turned off and restored, the relays will remain off (if the value is 0, or turn on those that were turned on before the power interruption if the register has a value of 1). This feature appeared in the modules with the firmware, starting with version 1.5.3. | ||
== | ==Modbus Control== | ||
Подробно о работе с модулем по протоколу Modbus написано в разделе [[Relay Module Modbus Management|Управление модулями реле Wirenboard по протоколу Modbus]]. | Подробно о работе с модулем по протоколу Modbus написано в разделе [[Relay Module Modbus Management|Управление модулями реле Wirenboard по протоколу Modbus]]. |
Версия 20:03, 16 июля 2019
WB-MRPS6 six-channel relay modules are designed for industrial and home automation systems. Modules, depending on the modification, are designed for switching the power load of General purpose, including inductive and capacitive: control of led lamps, incandescent lamps, pulse power supplies; for use in PDU, etc.
The modules are designed for a maximum current of 16A (rated load 10A) and can be used without intermediate contactors.
Models
The module is available in two versions (S) and (P), the difference between which is the maximum allowable switching current.
The naming scheme:
WB-MRPS6 | Relay output type |
---|---|
S | ultra-high starting current (relay with additional tungsten contacts) |
P | a high inrush current |
Technical specifications
Our detailed article in russian on habr.com about the choice of relay parameters for the switched load: https://habr.com/ru/company/wirenboard/blog/422197/
Parameter | Value |
---|---|
Power | |
Supply voltage | 9 — 24 V DC |
Power consumption |
|
"'Terminals and wire section'" | |
Recommended wire cross-section with NSUI, mm2 | 0,75 — 1 for control inputs, the 2.5 for power input |
Length of the standard sleeve NSVE, mm | 8 |
Torque of screws, N∙m | 0,2 for control inputs , 0,5 — for power inputs |
Outputs | |
Output type | Mechanical relay contacts |
Output configuration | 6 outputs that are connected to the relay contacts |
Configuration of each output contacts | Two-position, normally open (COM and NO) |
Maximum switching voltage, AC | 250 V |
Maximum switching voltage, DC | 30 Volts |
Maximum switching current per channel |
see table in #Relay parameters |
Contact resistance | < 100 milliohms |
Voltage isolation between the controller and the output | 1500 V (RMS value) |
Term life: | see table in #relay Parameters |
Inputs | |
none | |
Control | |
Management interface | RS-485 |
Interface isolation | Uninsulated |
Communication protocol | Modbus RTU, the address is set by software, factory settings are indicated on the label |
RS-485 interface parameters | set programmatically (see register Card); default: speed — 9600 bit/s; data — 8 bit; parity bit — none (N); stop bits — 2 |
Ready for operation after power supply | ~0.03 c |
dimensions | |
Width, DIN units | 3 |
Overall dimensions (l x W x h) | 53.3 x 90.2 x 57.5 mm |
Display | |
Power and data exchange indication | Green status led |
Relay channel status indication | Orange LEDs, 1 — 6 |
operating Conditions | |
Air temperature | |
Relative humidity | Up to 92%, no condensation |
Module dimensions
Relay
Modification S | Modification P | |
---|---|---|
Maximum switching current,
resistive load 230V AC |
16A | |
Maximum switching current,
resistive load 30V DC |
- | - |
Maximum switching power
for incandescent lamps (230V AC) |
"'3000W"' | 1000W |
Maximum allowable inrush current
(within 20ms, for no contact) |
"'165A"' | "'80A"' |
Maximum allowable inrush current
(within 200 µs, for no contact) |
"'800A"' | - |
Contact resistance | 100 milliohms | ? |
Contact material | "'W+AgSnO2"' | AgSnO |
Contact configuration | SPST (NO, COM) | |
Lifetime: number of switches
for load 16A 230V AC, cos φ = 1 |
12 000 | 50 000 |
Lifetime: number of switches
without load |
5 000 000 | 30 000 000 |
Relay model | Hongfa HF115F-S | TE Connectivity RT33L |
Peculiar properties | Very high starting current | High starting current |
Application | General purpose power load, inductive load,
capacitive load. Motors, contactors, incandescent lamps, LED lights, switching power supplies, etc. |
General purpose power load, inductive load,
capacitive load. Motors, contactors, incandescent lamps, switching power supplies, etc. |
Inputs
Model WB-MRPS6 is not equipped with discrete inputs.
Installation of modules
The relay module is mounted on a standard 35 mm wide DIN rail and occupies the width of 3 DIN modules.
Terminal blocks with 3.5 mm increments on the relay board are used to connect power and control lines (RS-485). The cross-section of wires connected to the screw terminals of the relay outputs must correspond to the power of the switched load: it is important not to exceed the recommended current — 16 A.
If the device is the last one on the RS-485 line, a 120 Ohm resistor-terminator must be installed between its inputs A and B. Practice shows that in case of bench tests with a small length of the RS-485 line and a small number of devices, terminator for the last device in the line is not necessary.
The module must be installed in such a way as to meet the requirements of electrical safety and to prevent accidental contact of contacts under high voltage. The module must be operated under recommended environmental conditions.
Relay operation in case of power failure
Depending on the value written to the storage register 0x06, after the power is turned off and restored, the relays will remain off (if the value is 0, or turn on those that were turned on before the power interruption if the register has a value of 1). This feature appeared in the modules with the firmware, starting with version 1.5.3.
Modbus Control
Подробно о работе с модулем по протоколу Modbus написано в разделе Управление модулями реле Wirenboard по протоколу Modbus. Там же можно найти карту регистров устройства.
Назад к списку периферийных устройств
Обновление прошивки устройства
Начиная с новых версий микропрограмм устройства поддерживается функционал обновления прошивки (микропрограммы) по протоколу Modbus. Это дает возможность расширять функциональные возможности устройств и устранять ошибки в микропрограммном обеспечении непосредственно на месте монтажа. Подробнее о перепрошивке устройств рассказано в статье Загрузка прошивок на устройства Wiren Board. Список версий прошивок, поддерживающих обновление, а также устройств, для которых эта функция реализована, можно найти в статье Firmware_Changelog.
Известные неисправности
Список известных неисправностей
Изображения и чертежи устройства
По ссылкам ниже вы можете скачать изображения и чертежи устройства WB-MRPS6/P.
Corel Draw 2018: WB-MRPS6_P.cdr.zip
Corel Draw PDF: WB-MRPS6_P.cdr.pdf
Autocad 2013 DXF: WB-MRPS6_P.dxf.zip
Autocad PDF: WB-MRPS6_P.pdf
По ссылкам ниже вы можете скачать изображения и чертежи устройства WB-MRPS6/S.
Corel Draw 2018: WB-MRPS6_S.cdr.zip
Corel Draw PDF: WB-MRPS6_S.cdr.pdf
Autocad 2013 DXF: WB-MRPS6_S.dxf.zip
Autocad PDF: WB-MRPS6_S.pdf