Translations:WB-M1W2 1-Wire to Modbus Temperature Measurement Module/15/en
Версия от 13:29, 19 июля 2019; RomanKulibaba (обсуждение | вклад) (Новая страница: «{| class="wikitable" ! rowspan="2" |Register/ address ! rowspan="2" |Type ! rowspan="2" |Read/ write ! rowspan="2" |Default ! rowspan="2" |Format ! rowspan="2" |P…»)
Register/ address | Type | Read/ write | Default | Format | Purpose | Versions
insertions |
---|---|---|---|---|---|---|
6 | input | R | 0x7FFF | °C × 16 (signed) | Temperature with built-in sensor | |
7 | input | R | 0x7FFF | °C × 16 (signed) | Temperature from the first external 1-Wire sensor | |
8 | input | R | 0x7FFF | °C × 16 (signed) | Temperature from second external 1-Wire sensor | |
20 | input | R | 0 | °C × 16 (signed) | Temperature from the first external 1-Wire sensor. In case of an error, the sensor retains the previous valid value (sensor status read from the discrete register 16). | starting with firmware 4.6.0 |
21 | input | R | 0 | °C × 16 (signed) | Temperature from the second external 1-Wire sensor. In case of an error, the sensor retains the previous valid value (sensor status read from the discrete register 17). | |
99 | holding | RW | 16 | 1 = 0.0625 C | (available from firmware version 3.10.0)
Suspicious value filter for 1-Wire sensors (85.000 C, 127.937 C). Values are discarded if the previous value differs from the suspect value by more than * 0.0625 C. Write 0 to disable the filter. |
3.10.0 |