Translations:Relay Module Modbus Management/18/en
Register / address | Type | Read-write | Default | Format | Appointment | Note |
---|---|---|---|---|---|---|
0 .. (x-1) | coil | RW | - | 1 or 0 | relay status with number 1 .. x | |
0 .. (y-1) | discrete | R | - | 1 or 0 | entry status with number 1 .. y | |
5 | holding | RW | 0 |
default value should be kept |
not used in modern firmware. In outdated versions of firmware was used to set mode of interaction of digital inputs with relay outputs for all inputs at once. |
not used in modern firmware. In outdated versions of firmware was used to set mode of interaction of digital inputs with relay outputs for all inputs at once. Configuration values were the same as now used in registers 9 .. (9+x-1), but applied to all inputs at once. |
6 | holding | RW |
|
relay operation mode in case of power failure | (only in firmware 1.5.3 and later) | |
8 | holding | RW | 0 | seconds | safe mode timeout |