Wbincludes:WB-REF-U Carel μRack Modbus Registers
Адрес | Тип | Формат | Имя | Назначение | Единицы измерения |
Значения | |||
---|---|---|---|---|---|---|---|---|---|
в Hex | в DEC | Минимум | Максимум | ||||||
0x0195 | 405 | input | s16 | LP1 | Probe B4 | 0.1bar | |||
0x0199 | 409 | input | s16 | HP/LP2 | Probe B1 | 0.1bar/0.1°C | |||
0x0196 | 406 | input | s16 | B2 | Probe B2 | 0.1°C/°F | -40 | 150 | |
0x0193 | 403 | input | s16 | B3 | Probe B3 | 0.1°C/°F | -40 | 150 | |
0x019C | 412 | holding | s16 | r01 | Suction set point circuit 1 | 0.1bar | |||
0x019A | 410 | holding | s16 | r02 | Differential circuit 1 | 0.1bar | 0 | 20 | |
0x019E | 414 | holding | s16 | r03 | Suction set point circuit 2 | 0.1bar | |||
0x019F | 415 | holding | s16 | r04 | Differential circuit 2 | 0.1bar | 0 | 20 | |
0x0197 | 407 | holding | s16 | r12 | Min suction set point 1 | 0.1bar | 0 | ||
0x019B | 411 | holding | s16 | r13 | Max suction set point 1 | 0.1bar | 40 | ||
0x019D | 413 | holding | s16 | r14 | Min suction set point 2 | 0.1bar | 0 | ||
0x0190 | 400 | holding | s16 | r15 | Max suction set point 2 | 0.1bar | 40 | ||
0x0198 | 408 | holding | s16 | r16(bar) | Fan set point (bar) | 0.1bar | |||
0x0192 | 402 | holding | s16 | r16 (°C) | Fan set point (°C) | 0.1°C/°F | |||
0x0191 | 401 | holding | s16 | r17 (bar) | Fan differential (bar) | 0.1bar | 0 | 20 | |
0x0194 | 404 | holding | s16 | r17(°C) | Fan differential (°C) | 0.1°C/°F | 0 | 20 | |
0x01A5 | 421 | holding | s16 | r25(bar) | Min fan set point (bar) | °F | 0 | ||
0x01A9 | 425 | holding | s16 | r25 (°C) | Min fan set point (°C) | 0.1°C/°F | 0 | ||
0x01A6 | 422 | holding | s16 | r26(bar) | Max fan set point (bar) | 0.1bar | 40 | ||
0x01A3 | 419 | holding | s16 | r26(°C) | Max fan set point (°C) | 0.1°C/°F | 150 | ||
0x01AC | 428 | holding | s16 | r18 (bar) | Fan inverter set point (bar) | 0.1bar | |||
0x01AA | 426 | holding | s16 | r18 (°C) | Fan inverter set point (°C) | 0.1°C/°F | |||
0x01AE | 430 | holding | s16 | r19 (bar) | Fan inverter differential | 0.1bar | 0 | 20 | |
0x01AF | 431 | holding | s16 | r19 (°C) | Fan inverter differential | 0.1°C/°F | 0 | 20 | |
0x01A7 | 423 | holding | s16 | A01 | HP suction 1 alarm threshold | 0.1bar | 40 | ||
0x01AB | 427 | holding | s16 | A03 | LP suction 1 alarm threshold | 0.1bar | -0.5 | 7 | |
0x01AD | 429 | holding | s16 | A05 | HP suction 2 alarm threshold | 0.1bar | 40 | ||
0x01A0 | 416 | holding | s16 | A07 | LP suction 2 alarm threshold | 0.1bar | -0.5 | 7 | |
0x01A8 | 424 | holding | s16 | A09 (bar) | HP discharge alarm threshold (bar) | 0.1bar | 40 | ||
0x01A2 | 418 | holding | s16 | A09 (°C) | HP discharge alarm threshold (°C) | 0.1°C/°F | 150 | ||
0x01A1 | 417 | holding | s16 | A10(bar) | LP discharge alarm threshold (bar) | 0.1bar | 0 | ||
0x01A4 | 420 | holding | s16 | A10 (°C) | LP discharge alarm threshold (°C) | 0.1°C/°F | 0 | ||
0x01B5 | 437 | holding | s16 | /23 | Suction probe 4 calibration | 0.1bar | -12 | 12 | |
0x01B9 | 441 | holding | s16 | /24 | Discharge probe 1 calibration | 0.1bar | -12 | 12 | |
0x01B6 | 438 | holding | s16 | /25 | Room probe 2 calibration | 0.1°C/°F | -12 | 12 | |
0x01B3 | 435 | holding | s16 | /26 | Outside probe 3 calibration | 0.1°C/°F | -12 | 12 | |
0x01BC | 444 | holding | s16 | /17 | Min value suction transducer | 0.1bar | -1 | ||
0x01BA | 442 | holding | s16 | /18 | Min value discharge transducer | 0.1bar | -1 | ||
0x01BE | 446 | holding | s16 | /19 | End scale value suction transducer | 0.1bar | 40 | ||
0x01BF | 447 | holding | s16 | /20 | End scale value discharge transducer | 0.1bar | 40 | ||
0x01B7 | 439 | holding | s16 | /33 | Set point prevent high pressure function | 0.1bar | 0 | 40 | |
0x01BB | 443 | holding | s16 | r34 | Set point offset to change set from DI | 0.1bar | -99 | 99 | |
0x01BD | 445 | holding | s16 | r11 | Differential pressure for dead band by time | 0.1bar | 0 | 20 | |
0x01B0 | 432 | holding | s16 | r33 | Condensing temperature delta for floating control | 0.1°C/°F | -40 | 150 | |
0x01B8 | 440 | holding | s16 | A16 | High temp threshold probe B2 | 0.1°C/°F | -40 | 150 | |
0x01B2 | 434 | holding | s16 | A17 | High temp threshold probe B3 | 0.1°C/°F | -40 | 150 | |
0x01B1 | 433 | holding | u16 | /00 | Type of unit | 0 | 2 | ||
0x01B4 | 436 | holding | u16 | /01 | Unit model | 0 | 14 | ||
0x01C5 | 453 | input | u16 | - | Number of compressors | 0 | 4 | ||
0x01C9 | 457 | holding | u16 | /09 | Number of fans | 0 | 4 | ||
0x01C6 | 454 | input | u16 | - | Unit status | 0 | 7 | ||
0x01C3 | 451 | holding | u16 | r07 | Minimum call time for compressor start (dead band) | s | 0 | 999 | |
0x01CC | 460 | holding | u16 | r09 | Minimum call time for compressor stop (dead band) | s | 0 | 999 | |
0x01CA | 458 | holding | u16 | C01 | Minimum compressor ON time | s | 0 | 999 | |
0x01CE | 462 | holding | u16 | C02 | Minimum compressor OFF time | s | 0 | 999 | |
0x01CF | 463 | holding | u16 | C03 | Minimum time between starts of different compressors | s | 0 | 999 | |
0x01C7 | 455 | holding | u16 | C05 | Minimum time between starts of the same compressor | s | 0 | 999 | |
0x01CB | 459 | holding | u16 | - | Fan start delay (dead band) | s | 0 | 999 | |
0x01CD | 461 | holding | u16 | - | Fan stop delay (dead band) | s | 0 | 999 | |
0x01C0 | 448 | holding | u16 | A18 | Liquid level alarm delay | s | 0 | 999 | |
0x01C8 | 456 | holding | u16 | - | Minimum fan speed | % | 0 | 100 | |
0x01C2 | 450 | holding | u16 | /07 | Number of compressors on in circuit 1 with probe damaged | 0 | 4 | ||
0x01C1 | 449 | holding | u16 | /08 | Number of compressors on in circuit 2 with probe damaged | 0 | 2 | ||
0x01C4 | 452 | holding | u16 | /12 | Number of fans on with probe damaged | 0 | 4 | ||
0x01D5 | 469 | input | u16 | - | Version of the application | ||||
0x01D9 | 473 | holding | u16 | /35 | Type of refrigerant | 0 | 11 | ||
0x01D6 | 470 | holding | u16 | /03 | Capacity of compressor 1 | 0 | 500 | ||
0x01D3 | 467 | holding | u16 | /04 | Capacity of compressor 2 | 0 | 500 | ||
0x01DC | 476 | holding | u16 | /05 | Capacity of compressor 3 | 0 | 500 | ||
0x01DA | 474 | holding | u16 | /06 | Capacity of compressor 4 | 0 | 500 | ||
0x01DE | 478 | input | u16 | /11 | Inverter readout % | % | 0 | 100 | |
0x01DF | 479 | holding | u16 | /15 | Multifunction DI configuration | 0 | 12 | ||
0x01D7 | 471 | holding | u16 | /16 | Type of discharge probe | 0 | 2 | ||
0x01DB | 475 | holding | u16 | /21 | Type of probe B2 | 0 | 2 | ||
0x01DD | 477 | holding | u16 | /22 | Type of probe B3 | 0 | 2 | ||
0x01D0 | 464 | holding | u16 | /37 | Delay restart after black out | s | 0 | 999 | |
0x01D8 | 472 | holding | u16 | C04 | Min time between two stop calls for different compressors | s | 0 | 999 | |
0x01D2 | 466 | holding | u16 | C06 | Time between compressor stop call with Prevent function | s | 0 | 999 | |
0x01D1 | 465 | holding | u16 | C07 | Operating hour threshold for maintenance | h x10 | 0 | 999 | |
0x01D4 | 468 | input | u16 | C08 | Compressor 1 hours | h x10 | 0 | 999 | |
0x01E5 | 485 | input | u16 | C10 | Compressor 2 hours | h x10 | 0 | 999 | |
0x01E9 | 489 | input | u16 | C12 | Compressor 3 hours | h x10 | 0 | 999 | |
0x01E6 | 486 | input | u16 | C14 | Compressor 4 hours | h x10 | 0 | 999 | |
0x01E3 | 483 | holding | u16 | r05 | Type of compressor rotation | 0 | 2 | ||
0x01EC | 492 | holding | u16 | r06 | Type of compressor control | 0 | 2 | ||
0x01EA | 490 | holding | u16 | r08 | Maximum call for compressor starts in dead band by time | s | 0 | 999 | |
0x01EE | 494 | holding | u16 | r10 | Maximum call for compressor stops in dead band by time | s | 0 | 999 | |
0x01EF | 495 | holding | u16 | r20 | Type of fan rotation | 0 | 1 | ||
0x01E7 | 487 | holding | u16 | r21 | Type of fan control | 0 | 2 | ||
0x01EB | 491 | holding | u16 | r22 | Integral time for P+I fan control | s | 0 | 999 | |
0x01ED | 493 | holding | u16 | r23 | Time between 2 fans starts in dead band | s | 0 | 999 | |
0x01E0 | 480 | holding | u16 | r24 | Time between 2 fans stops in dead band | s | 0 | 999 | |
0x01E8 | 488 | holding | u16 | r27 | Inverter speed up time | s | 0 | 999 | |
0x01E2 | 482 | holding | u16 | r28 | Inverter ramp up time | s | 0 | 999 | |
0x01E1 | 481 | holding | u16 | r29 | Minimum inverter output | % | 0 | 100 | |
0x01E4 | 484 | holding | u16 | r30 | Maximum inverter output | % | 0 | 100 | |
0x01F5 | 501 | holding | u16 | r31 | Triac impulse duration | ms | 0 | 10 | |
0x01F9 | 505 | holding | u16 | A02 | High suction pressure 1 alarm delay | s | 0 | 999 | |
0x01F6 | 502 | holding | u16 | A04 | Low suction pressure 1 alarm delay | s | 0 | 999 | |
0x01F3 | 499 | holding | u16 | A06 | High suction pressure 2 alarm delay | s | 0 | 999 | |
0x01FC | 508 | holding | u16 | A08 | Low suction pressure 2 alarm delay | s | 0 | 999 | |
0x01FA | 506 | holding | u16 | A11 | Low discharge pressure alarm delay | s | 0 | 999 | |
0x01FE | 510 | holding | u16 | A12 | Compressor thermal overload alarm delay | s | 0 | 999 | |
0x01FF | 511 | holding | u16 | A13 | Prevent time in which no compressor starts are enabled | m | 0 | 99 | |
0x01F7 | 503 | holding | u16 | A14 | Prevent time in which the activation signals the alarm | m | 0 | 999 | |
0x01FB | 507 | holding | u16 | A15 | Time to reset prevent alarm | m | 0 | 99 | |
0x01FD | 509 | holding | u16 | A20 | Alarm signal delay | s | 0 | 999 | |
0x01F0 | 496 | holding | u16 | A21 | Time to change low pressure alarm from automatic to manual | s | 0 | 999 | |
0x01F1 | 497 | input | u16 | Operating percentage of first capacity controlled compressor | |||||
0x01F4 | 500 | input | u16 | Operating percentage of second capacity controlled compressor | |||||
0x07 | 7 | coil | bool | Unit on | |||||
0x00 | 0 | discrete | bool | Status of compressor 1 | |||||
0x0D | 13 | discrete | bool | Status of compressor 2 | |||||
0x08 | 8 | discrete | bool | Status of compressor 3 | |||||
0x0B | 11 | discrete | bool | Status of compressor 4 | |||||
0x04 | 4 | discrete | bool | Status of fan 1 | |||||
0x01 | 1 | discrete | bool | Status of fan 2 | |||||
0x09 | 9 | discrete | bool | Status of fan 3 | |||||
0x0C | 12 | discrete | bool | Status of fan 4 | |||||
0x03 | 3 | discrete | bool | Status of digital input 1 | |||||
0x06 | 6 | discrete | bool | Status of digital input 2 | |||||
0x0F | 15 | discrete | bool | Status of digital input 3 | |||||
0x0A | 10 | discrete | bool | Status of digital input 4 | |||||
0x0E | 14 | discrete | bool | Status of digital input 5 | |||||
0x02 | 2 | coil | bool | A19 | Reset alarms | ||||
0x05 | 5 | coil | bool | /14 | Digital input logic | ||||
0x017 | 23 | coil | bool | /28 | Alarm relay logic | ||||
0x010 | 16 | coil | bool | /10 | Enable fan inverter | ||||
0x01D | 29 | coil | bool | /38 | ON/OFF from supervisor | ||||
0x018 | 24 | coil | bool | /32 | Enable 'prevent' control on condenser | ||||
0x01B | 27 | coil | bool | /02 | Enable management of different compressors | ||||
0x014 | 20 | coil | bool | /29 | Type of compressor reset | ||||
0x011 | 17 | coil | bool | /30 | Type of fan reset | ||||
0x019 | 25 | coil | bool | /31 | Type of reset for general high press. Switch | ||||
0x01C | 28 | coil | bool | C09 | Reset compressor 1 hours | ||||
0x013 | 19 | coil | bool | C11 | Reset compressor 2 hours | ||||
0x016 | 22 | coil | bool | C13 | Reset compressor 3 hours | ||||
0x01F | 31 | coil | bool | C15 | Reset compressor 4 hours | ||||
0x01A | 26 | coil | bool | r32 | Enable floating condenser control | ||||
0x01E | 30 | coil | bool | A22 | Enable unit Off due to probe fault | ||||
0x012 | 18 | coil | bool | /13 | Enable fan with comp on | ||||
0x015 | 21 | discrete | bool | A01 | Alarm: compressor 1 | ||||
0x027 | 39 | discrete | bool | A02 | Alarm: compressor 2 | ||||
0x020 | 32 | discrete | bool | A03 | Alarm: compressor 3 | ||||
0x02D | 45 | discrete | bool | A04 | Alarm: compressor 4 | ||||
0x028 | 40 | discrete | bool | A22 | Alarm: fan 1 | ||||
0x02B | 43 | discrete | bool | A23 | Alarm: fan 2 | ||||
0x024 | 36 | discrete | bool | A24 | Alarm: fan 3 | ||||
0x021 | 33 | discrete | bool | A25 | Alarm: fan 4 | ||||
0x029 | 41 | discrete | bool | A09 | Alarm: liquid level | ||||
0x02C | 44 | discrete | bool | A10 | Alarm: general low suction pressure 1 (from multifunction DI) | ||||
0x023 | 35 | discrete | bool | A11 | Alarm: general low suction pressure 2 (from multifunction DI) | ||||
0x026 | 38 | discrete | bool | A13 | Alarm: low discharge pressure | ||||
0x02F | 47 | discrete | bool | A14 | Alarm: high discharge pressure | ||||
0x02A | 42 | discrete | bool | A15 | Alarm: low suction pressure 1 | ||||
0x02E | 46 | discrete | bool | A16 | Alarm: high suction pressure 1 | ||||
0x022 | 34 | discrete | bool | A17 | Alarm: low suction pressure 2 | ||||
0x025 | 37 | discrete | bool | A18 | Alarm: high suction pressure 2 | ||||
0x037 | 55 | discrete | bool | A20 | Probe B1 faulty or disconnected | ||||
0x030 | 48 | discrete | bool | AB2 | Probe B2 faulty or disconnected | ||||
0x03D | 61 | discrete | bool | AB3 | Probe B3 faulty or disconnected | ||||
0x038 | 56 | discrete | bool | A19 | Probe B4 faulty or disconnected | ||||
0x03B | 59 | discrete | bool | A05 | Compressor 1 maintenance | ||||
0x034 | 52 | discrete | bool | A06 | Compressor 2 maintenance | ||||
0x031 | 49 | discrete | bool | A07 | Compressor 3 maintenance | ||||
0x039 | 57 | discrete | bool | A08 | Compressor 4 maintenance | ||||
0x03C | 60 | discrete | bool | A12 | General discharge pressure switch (from multifunction DI) | ||||
0x033 | 51 | discrete | bool | A26 | General fan thermal overload | ||||
0x036 | 54 | discrete | bool | A27 | Prevent high discharge pressure | ||||
0x03F | 63 | discrete | bool | A28 | Compressors off due to prevent | ||||
0x03A | 58 | discrete | bool | A29 | Excessive prevent frequency | ||||
0x03E | 62 | discrete | bool | HtE | High outside temperature | ||||
0x032 | 50 | discrete | bool | HtA | High room temperature |