Register / address Type Read-write Default Format Appointment Note
0 .. (x-1) coil RW - 1 or 0 relay status with number 1 .. x
0 .. (y-1) discrete R - 1 or 0 entry status with number 1 .. y
5 holding RW 0
  • 0: buttons without locking
  • 1: switch with lock
  • 3: disable interaction
mode of interaction of digital inputs with relay outputs. The input status registers and the pressure counter continue to operate in all modes. The register was used in the old configuration mechanism. It is recommended to leave it set to 0 and the inputs are configured via the individual registers 9 .. (9+x-1)
6 holding RW
  • 0: do not restore relay state after power is restored
  • 1: restore relay state after power is restored
relay operation mode in case of power failure (only in firmware 1.5.3 and later)
8 holding RW 0 seconds safe mode timeout