Register/ address Type Read/ write default or error Value Format Purpose Supported in From version

insertions

WB-MS (model code) WB-MS v2 (model code) WB-MSW WB-MSW2 WB-MSW V. 3
0 input R 0x7FFF °C × 10 (signed) Temperature with built-in sensor T - - + +
1 input R

%RH × 10 (signed)

relative humidity with built-in sensor H - + + +
2 input R - LC "(register is not used in WB-MSW sensors, registers 9 and 10 instead)"
Illumination from built-in sensor
L Lux - - -
3 input R - dB × 100 Noise level multiplied by 100 S - + S S
4 input R 0x7FFF °C × 100 (signed) Temperature with built-in sensor + + - - + 4.2
5 input R - %RH × 100 (signed) Relative humidity with built-in sensor + + - - + 4.2
6 input R 0x7FFF °C × 16 (signed) Temperature from external sensor D + - - -
7 input R 0x7FFF °C × 16 (signed) Temperature from external sensor D + - - -
8 input R 0xFFFF PPM CO2 concentration - - After C
9-10 input R LC The illumination, multiplied by 100 (9 - high-order, 10 — LSB luminance values) - - + L
11 input R 0xFFFF PPM Air quality - VOC - - +
88 holding RW 0 ppm (400-1500) Service register, doesn't present in most devices. Manual calibration of CO2 sensor. For calibration, write down here the current CO2 concentration measured by another instrument - - - C C 3.12
89 holding RW 0xFF days' Service register, doesn't present in most devices. Cycle time for co sensor self-calibration algorithm (ABC) - - - C C 3.12
90 holding RW 20 (200 ms) × 10 ms light averaging Time

L, B

- - - -
91 holding RW 20 (200 ms) × 10 ms Noise averaging time S - + S S
95 holding RW 1 1 or 0 CO2 sensor (ABC) auto-calibration to atmospheric CO2 - - - After C
96 holding R 2000 / 5000 ppm (available from firmware version 3.5.0) CO2 concentration measurement Range. Valid values: 2000, 5000, 10000. - - - C C 3.5.0