Translations:WB-MIR v2 - Modbus IR Remote Control/16/en
|-
|110
|holding
|RW
|96
|baud rate / 100
|RS-485 port speed, "'divided by 100"'. Permissible speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
(configure RS-485 communication parameters for Wiren Board Modbus devices)
| rowspan="3" |>3.1.0
|-
|111
|holding
|RW
|0
|
|configure the RS-485 port parity bit. Valid values: 0 - no parity bit (none), 1 - odd (odd), 2 - even (even)
|-
|112
|holding
|RW
|2
|
|number of stop bits of RS-485 port. Valid values: 1, 2
|-
|
|
|
|
|
|
|
|-
|120 (0x78)
|holding
|RW
|0
|other than 0
|write to the register causes a reset of the module without saving state
|
|-
|121 (0x79)
|input
|R
| -
|mV
|current supply voltage of the module
|
|-
|128 (0x80)
|holding
|RW
|1
|
|The Modbus address of the device
|
|-
| 129 (0x81) || holding || RW|| 0 || 0 or 1 || Switch to bootloader mode || starting with firmware 4.5.0
|-
|200-206
|input
|R
|see device Signature
|
|signature
|
|-
|220-241
|input
|R
|
|__date__ _ _ time__
|the build date of the firmware
|
|-
|245
|holding
|RW
|216
|°C × 100 (signed)
|Self-heating compensation of the built-in temperature sensor.
The register value is subtracted from the temperature measured by the built-in sensor (register 6)
|
|-
|250-269
|input
|R
|
|string, null-terminated
|firmware version
|
|-
|270-271
|input
|R
|
|32-bit unsigned int
|unique identifier (S/N)
|
|-
|
|
|
|
|
|
|
|-
|275
|holding
|RW
|0
|0 or 1
|1-W input mode: 0 - 1-wire, 1 - discrete input
| rowspan="3" |>=4.0.0
|-
|277
|input
|R
|
|16-bit unsigned int
|Counter for 1-W input
|-
|0
|discrete
|R
|
|0 or 1
|Current state of input 1-W: 0 - open, 1 - GND closed. If 1-wire mode is selected for input, the value is always 0.
|-
|16
|discrete
|R
|
|0 or 1
|Sensor polling status 1-Wire input no. 1: 0 - sensor not connected, 1 - sensor connected and correctly polled
|starting with firmware v.4.6.0
|}