WB-MAI11 Modbus Analog Inputs/en: различия между версиями

Новая страница: «Measuring the voltage from a thermocouple (diagram in Fig.4) |1 |± 2048 mV | rowspan="3" |±0.2% |- |2 |± 1024 mV |- |4 |± 512 mV |- |8 |± 256 mV | rowspan="5…»
(Новая страница: «Voltage measurement from 0 to 5V (diagram in Fig.2) |1 |0...(+5V) | rowspan="3" |±0.1% | rowspan="6" |% · 100 |- |2 |0...(+5V / 2) |- |4 |0...(+5V / 4) |- | row…»)
(Новая страница: «Measuring the voltage from a thermocouple (diagram in Fig.4) |1 |± 2048 mV | rowspan="3" |±0.2% |- |2 |± 1024 mV |- |4 |± 512 mV |- |8 |± 256 mV | rowspan="5…»)
Строка 589: Строка 589:
| rowspan="8" |differential voltage Measurement from -2 V to 2 V (diagram in Fig.1)
| rowspan="8" |differential voltage Measurement from -2 V to 2 V (diagram in Fig.1)


Измерение напряжения с термопары (схема на рис. 4)
Measuring the voltage from a thermocouple (diagram in Fig.4)
|1
|1
|± 2048 мВ
|± 2048 mV
| rowspan="3" |±0.2%
| rowspan="3" |±0.2%
|-
|-
|2
|2
|± 1024 мВ
|± 1024 mV
|-
|-
|4
|4
|± 512 мВ
|± 512 mV
|-
|-
|8
|8
|± 256 мВ
|± 256 mV
| rowspan="5" |±0.25%
| rowspan="5" |±0.25%
|-
|-
|16
|16
|± 128 мВ
|± 128 mV
|-
|-
|32
|32
|± 64 мВ
|± 64 mV
|-
|-
|64
|64
|± 32 мВ
|± 32 mV
|-
|-
|128
|128
|± 16 мВ
|± 16 mV
|-
|-
| rowspan="9" |Измерение
| rowspan="9" | Resistance measurement
сопротивления
 
| rowspan="3" |Нормальный
| rowspan="3" |Normal
для входов INxP
for INxP inputs
| rowspan="6" |0x0002
| rowspan="6" |0x0002
| rowspan="6" |2
| rowspan="6" |2
| rowspan="6" |Измерение сопротивления по двухпроводной схеме (схема на рис. 5)
| rowspan="6" |Resistance measurement using two-wire circuit (diagram in Fig.5)


Подключение датчиков типа "сухой контакт" (схема на рис. 5)
Подключение датчиков типа "сухой контакт" (схема на рис. 5)
12 063

правки