'''Address change''' is broadcast (slave_id 0) team record (WRITE_SINGLE_REGISTER) to holding register with address 128 (0x80).
'''Address change''' is broadcast (slave_id 0) team record (WRITE_SINGLE_REGISTER) to holding register with address 128 (0x80).


По адресу 200 лежит '''сигнатура''' длинной 6 байт. Сигнатура уникальна для каждой модели устройства и позволяет идентифицировать модель.
The 6-byte module signature is stored at address 200. The signature is unique for each model of Wiren Board devices and allows to identify the model.
Для получения сигнатуры нужно выполнить READ_HOLDING_REGISTERS адрес 200 длина 6.   
To obtain the signatures necessary to fulfill READ_HOLDING_REGISTERS address 200 length 6.   
Запись в эту область памяти не поддерживается, при попытки записи в недопустимое место возвращается ошибка 3.
Writing to this area of memory is not supported and error 3 is returned when attempting to write to an invalid location.