12 063
правки
(Новая страница: «When flashing at the factory, the signature — the name of the hardware type of the device — is recorded into the memory of the device. When overwriting the fi…») |
(Новая страница: «The device loader receives firmware via Modbus RTU. In the bootloader mode, the communication parameters are fixed and do not depend on the previous values in the…») |
||
Строка 37: | Строка 37: | ||
The device loader receives firmware via Modbus RTU. In the bootloader mode, the communication parameters are fixed and do not depend on the previous values in the device memory: 9600 8N2. According to the Modbus protocol, the device can be set to bootloader mode, if 1 is written to the holding register 129 (0x81) during the operation of the main program. In this scenario, the device restarts and remains in bootloader mode for 120 seconds. | |||
Modbus-адрес устройства для прошивки в режиме загрузчика следует выбирать следующим образом: | Modbus-адрес устройства для прошивки в режиме загрузчика следует выбирать следующим образом: |