12 063
правки
(Новая страница: «Work features of the applied chip DS2484 and protection circuits are the causes. The protection circuit limits the signal fronts when the DS2484 active pullup is…») |
(Новая страница: «====Workarounds==== Use ports W1, W2 on the Wiren Board 6 when problems occur. Apply for a warranty replacement for a new version of the module.») |
||
Строка 53: | Строка 53: | ||
The chip also has a small sampling time, which makes its operation more sensitive to the steepness of the fronts, and therefore to the length of the line. | The chip also has a small sampling time, which makes its operation more sensitive to the steepness of the fronts, and therefore to the length of the line. | ||
==== | ====Workarounds==== | ||
Use ports W1, W2 on the Wiren Board 6 when problems occur. | |||
Apply for a warranty replacement for a new version of the module. | |||
====Запланированное исправление==== | ====Запланированное исправление==== | ||
Не планируется. WBE2-I-1WIRE снят с производство, к выходу планируется модуль WBE2-I-1WIRE-V2, не имеющий этой проблемы. | Не планируется. WBE2-I-1WIRE снят с производство, к выходу планируется модуль WBE2-I-1WIRE-V2, не имеющий этой проблемы. |