12 063
правки
(Новая страница: «Clear the contents of "/etc/ssmtp/ssmtp.conf" and fill in such lines, replacing the data with your own: <syntaxhighlight lang="linux-config"> mailhub=smtp.gmail.c…») |
(Новая страница: «== = Pre-setting for sending SMS== Make sure you insert the SIM card and connect the GSM antenna. == = Configure the notification module== #Go to the "Configs - A…») |
||
Строка 28: | Строка 28: | ||
In case of additional questions, see [http://askubuntu.com/questions/185070/why-i-get-hostname-name-or-service-not-known-error] and [https://wiki.archlinux.org/index.php/SSMTP]. | In case of additional questions, see [http://askubuntu.com/questions/185070/why-i-get-hostname-name-or-service-not-known-error] and [https://wiki.archlinux.org/index.php/SSMTP]. | ||
== | <div class="mw-translate-fuzzy"> | ||
== = Pre-setting for sending SMS== | |||
== | Make sure you insert the SIM card and connect the GSM antenna. | ||
# | == = Configure the notification module== | ||
# | #Go to the "Configs - Alarm Configuraion" page of the web interface. | ||
#* | #Add notification recipients in the "Recipients" section: | ||
#* | #*press "+ Recipient"; | ||
#* | #*select the type ("E-mail" or "SMS")); | ||
# | #*enter your postal address or phone number. You can also specify the subject of the email. | ||
#* | #Configure the parameter and condition to be checked in the "Alarms" section: | ||
#* | #*press "+ Item"; | ||
#*# | #*in the section that appears, select one of the four notification types from the drop-down list: | ||
#*# | #*#"Expected Value Alarm" - notification, if the value is no longer equal to the specified value. | ||
#*# | #*#"Minimum Value Alarm" - notification if the value becomes less than the specified value. | ||
#*# | #*#"Maximum Value Alarm" - notification if the value becomes greater than the specified value. | ||
#* | #*#"Minimum&Maximum Value Alarm" - notification if the value is out of the specified range. | ||
#* | #*in "Alarm name" enter an arbitrary name for the notification; | ||
#* | #*in "Cell", enter the parameter you want to monitor. The parameter is specified as "Device/Control", where the device and Control names for each parameter can be found on the "Settings" page of the web interface in the "MQTT Channels" table. For example, for a 1-Wire sensor connected to an external Modbus WB-MS sensor, this string would look like "wb-ms-thls-v2_101/External Sensor 2"; | ||
#* | #*in "Alarm activation message" enter the text of the message to be sent. You can enter two curly brackets "{} " in it in any place, instead of which a new parameter value will be substituted in the message, which is monitored. | ||
#* | #*depending on the notification type, fill in the fields "Minimum Value", "Maximum Value", "Expected Value"; | ||
# | #*some additional settings will be available if you click on the "Properties" button and check them. | ||
#* | #Click "Save" at the top of the page: | ||
#* | #*if you forget to specify some required parameter, the "Save" button will be inactive, and an error will be written next to the parameter in red, which should be corrected; | ||
#*if everything is OK, notifications will start working. | |||
</div> | |||
==Как настроить уведомления с более сложными условиями== | ==Как настроить уведомления с более сложными условиями== |
правки