WB-REF-U-CR Modbus Registers: различия между версиями

Нет описания правки
Строка 1694: Строка 1694:
|-
|-
|}
|}
== uRack ==
{{Wbincludes:Carel Modbus Register Table Header}}
| 0x0195
| style="text-align:right;" | 405
| input
| u16
| LP1
| Probe B4
| bar
| style="text-align:right;" |
| style="text-align:right;" |
|-
| 0x0199
| style="text-align:right;" | 409
| input
| u16
| HP/LP2
| Probe B1
| bar/°C
| style="text-align:right;" |
| style="text-align:right;" |
|-
| 0x0196
| style="text-align:right;" | 406
| input
| u16
| B2
| Probe B2
| °C/°F
| style="text-align:right;" | -40
| style="text-align:right;" | 150
|-
| 0x0193
| style="text-align:right;" | 403
| input
| u16
| B3
| Probe B3
| °C/°F
| style="text-align:right;" | -40
| style="text-align:right;" | 150
|-
| 0x019C
| style="text-align:right;" | 412
| holding
| u16
| r01
| Suction set point circuit 1
| bar
| style="text-align:right;" |
| style="text-align:right;" |
|-
| 0x019A
| style="text-align:right;" | 410
| holding
| u16
| r02
| Differential circuit 1
| bar
| style="text-align:right;" | 0
| style="text-align:right;" | 20
|-
| 0x019E
| style="text-align:right;" | 414
| holding
| u16
| r03
| Suction set point circuit 2
| bar
| style="text-align:right;" |
| style="text-align:right;" |
|-
| 0x019F
| style="text-align:right;" | 415
| holding
| u16
| r04
| Differential circuit 2
| bar
| style="text-align:right;" | 0
| style="text-align:right;" | 20
|-
| 0x0197
| style="text-align:right;" | 407
| holding
| u16
| r12
| Min suction set point 1
| bar
| style="text-align:right;" | 0
| style="text-align:right;" |
|-
| 0x019B
| style="text-align:right;" | 411
| holding
| u16
| r13
| Max suction set point 1
| bar
| style="text-align:right;" |
| style="text-align:right;" | 40
|-
| 0x019D
| style="text-align:right;" | 413
| holding
| u16
| r14
| Min suction set point 2
| bar
| style="text-align:right;" | 0
| style="text-align:right;" |
|-
| 0x0190
| style="text-align:right;" | 400
| holding
| u16
| r15
| Max suction set point 2
| bar
| style="text-align:right;" |
| style="text-align:right;" | 40
|-
| 0x0198
| style="text-align:right;" | 408
| holding
| u16
| r16(bar)
| Fan set point (bar)
| bar
| style="text-align:right;" |
| style="text-align:right;" |
|-
| 0x0192
| style="text-align:right;" | 402
| holding
| u16
| r16 (°C)
| Fan set point (°C)
| °C/°F
| style="text-align:right;" |
| style="text-align:right;" |
|-
| 0x0191
| style="text-align:right;" | 401
| holding
| u16
| r17 (bar)
| Fan differential (bar)
| bar
| style="text-align:right;" | 0
| style="text-align:right;" | 20
|-
| 0x0194
| style="text-align:right;" | 404
| holding
| u16
| r17(°C)
| Fan differential (°C)
| °C/°F
| style="text-align:right;" | 0
| style="text-align:right;" | 20
|-
| 0x01A5
| style="text-align:right;" | 421
| holding
| u16
| r25(bar)
| Min fan set point (bar)
| °F
| style="text-align:right;" | 0
| style="text-align:right;" |
|-
| 0x01A9
| style="text-align:right;" | 425
| holding
| u16
| r25 (°C)
| Min fan set point (°C)
| °C/°F
| style="text-align:right;" | 0
| style="text-align:right;" |
|-
| 0x01A6
| style="text-align:right;" | 422
| holding
| u16
| r26(bar)
| Max fan set point (bar)
| bar
| style="text-align:right;" |
| style="text-align:right;" | 40
|-
| 0x01A3
| style="text-align:right;" | 419
| holding
| u16
| r26(°C)
| Max fan set point (°C)
| °C/°F
| style="text-align:right;" |
| style="text-align:right;" | 150
|-
| 0x01AC
| style="text-align:right;" | 428
| holding
| u16
| r18 (bar)
| Fan inverter set point (bar)
| bar
| style="text-align:right;" |
| style="text-align:right;" |
|-
| 0x01AA
| style="text-align:right;" | 426
| holding
| u16
| r18 (°C)
| Fan inverter set point (°C)
| °C/°F
| style="text-align:right;" |
| style="text-align:right;" |
|-
| 0x01AE
| style="text-align:right;" | 430
| holding
| u16
| r19 (bar)
| Fan inverter differential
| bar
| style="text-align:right;" | 0
| style="text-align:right;" | 20
|-
| 0x01AF
| style="text-align:right;" | 431
| holding
| u16
| r19 (°C)
| Fan inverter differential
| °C/°F
| style="text-align:right;" | 0
| style="text-align:right;" | 20
|-
| 0x01A7
| style="text-align:right;" | 423
| holding
| u16
| A01
| HP suction 1 alarm threshold
| bar
| style="text-align:right;" |
| style="text-align:right;" | 40
|-
| 0x01AB
| style="text-align:right;" | 427
| holding
| u16
| A03
| LP suction 1 alarm threshold
| bar
| style="text-align:right;" | -0.5
| style="text-align:right;" | 7
|-
| 0x01AD
| style="text-align:right;" | 429
| holding
| u16
| A05
| HP suction 2 alarm threshold
| bar
| style="text-align:right;" |
| style="text-align:right;" | 40
|-
| 0x01A0
| style="text-align:right;" | 416
| holding
| u16
| A07
| LP suction 2 alarm threshold
| bar
| style="text-align:right;" | -0.5
| style="text-align:right;" | 7
|-
| 0x01A8
| style="text-align:right;" | 424
| holding
| u16
| A09 (bar)
| HP discharge alarm threshold (bar)
| bar
| style="text-align:right;" |
| style="text-align:right;" | 40
|-
| 0x01A2
| style="text-align:right;" | 418
| holding
| u16
| A09 (°C)
| HP discharge alarm threshold (°C)
| °C/°F
| style="text-align:right;" |
| style="text-align:right;" | 150
|-
| 0x01A1
| style="text-align:right;" | 417
| holding
| u16
| A10(bar)
| LP discharge alarm threshold (bar)
| bar
| style="text-align:right;" | 0
| style="text-align:right;" |
|-
| 0x01A4
| style="text-align:right;" | 420
| holding
| u16
| A10 (°C)
| LP discharge alarm threshold (°C)
| °C/°F
| style="text-align:right;" | 0
| style="text-align:right;" |
|-
| 0x01B5
| style="text-align:right;" | 437
| holding
| u16
| /23
| Suction probe 4 calibration
| bar
| style="text-align:right;" | -12
| style="text-align:right;" | 12
|-
| 0x01B9
| style="text-align:right;" | 441
| holding
| u16
| /24
| Discharge probe 1 calibration
| bar
| style="text-align:right;" | -12
| style="text-align:right;" | 12
|-
| 0x01B6
| style="text-align:right;" | 438
| holding
| u16
| /25
| Room probe 2 calibration
| °C/°F
| style="text-align:right;" | -12
| style="text-align:right;" | 12
|-
| 0x01B3
| style="text-align:right;" | 435
| holding
| u16
| /26
| Outside probe 3 calibration
| °C/°F
| style="text-align:right;" | -12
| style="text-align:right;" | 12
|-
| 0x01BC
| style="text-align:right;" | 444
| holding
| u16
| /17
| Min value suction transducer
| bar
| style="text-align:right;" | -1
| style="text-align:right;" |
|-
| 0x01BA
| style="text-align:right;" | 442
| holding
| u16
| /18
| Min value discharge transducer
| bar
| style="text-align:right;" | -1
| style="text-align:right;" |
|-
| 0x01BE
| style="text-align:right;" | 446
| holding
| u16
| /19
| End scale value suction transducer
| bar
| style="text-align:right;" |
| style="text-align:right;" | 40
|-
| 0x01BF
| style="text-align:right;" | 447
| holding
| u16
| /20
| End scale value discharge transducer
| bar
| style="text-align:right;" |
| style="text-align:right;" | 40
|-
| 0x01B7
| style="text-align:right;" | 439
| holding
| u16
| /33
| Set point prevent high pressure function
| bar
| style="text-align:right;" | 0
| style="text-align:right;" | 40
|-
| 0x01BB
| style="text-align:right;" | 443
| holding
| u16
| r34
| Set point offset to change set from DI
| bar
| style="text-align:right;" | -99
| style="text-align:right;" | 99
|-
| 0x01BD
| style="text-align:right;" | 445
| holding
| u16
| r11
| Differential pressure for dead band by time
| bar
| style="text-align:right;" | 0
| style="text-align:right;" | 20
|-
| 0x01B0
| style="text-align:right;" | 432
| holding
| u16
| r33
| Condensing temperature delta for floating control
| °C/°F
| style="text-align:right;" | -40
| style="text-align:right;" | 150
|-
| 0x01B8
| style="text-align:right;" | 440
| holding
| u16
| A16
| High temp threshold probe B2
| °C/°F
| style="text-align:right;" | -40
| style="text-align:right;" | 150
|-
| 0x01B2
| style="text-align:right;" | 434
| holding
| u16
| A17
| High temp threshold probe B3
| °C/°F
| style="text-align:right;" | -40
| style="text-align:right;" | 150
   
|-
| 0x01B1
| style="text-align:right;" | 433
| holding
| u16
| /00
| Type of unit
|
| style="text-align:right;" | 0
| style="text-align:right;" | 2
|-
| 0x01B4
| style="text-align:right;" | 436
| holding
| u16
| /01
| Unit model
|
| style="text-align:right;" | 0
| style="text-align:right;" | 14
|-
| 0x01C5
| style="text-align:right;" | 453
| input
| u16
| -
| Number of compressors
|
| style="text-align:right;" | 0
| style="text-align:right;" | 4
|-
| 0x01C9
| style="text-align:right;" | 457
| holding
| u16
| /09
| Number of fans
|
| style="text-align:right;" | 0
| style="text-align:right;" | 4
|-
| 0x01C6
| style="text-align:right;" | 454
| input
| u16
| -
| Unit status
|
| style="text-align:right;" | 0
| style="text-align:right;" | 7
|-
| 0x01C3
| style="text-align:right;" | 451
| holding
| u16
| r07
| Minimum call time for compressor start (dead band)
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01CC
| style="text-align:right;" | 460
| holding
| u16
| r09
| Minimum call time for compressor stop (dead band)
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01CA
| style="text-align:right;" | 458
| holding
| u16
| C01
| Minimum compressor ON time
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01CE
| style="text-align:right;" | 462
| holding
| u16
| C02
| Minimum compressor OFF time
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01CF
| style="text-align:right;" | 463
| holding
| u16
| C03
| Minimum time between starts of different compressors
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01C7
| style="text-align:right;" | 455
| holding
| u16
| C05
| Minimum time between starts of the same compressor
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01CB
| style="text-align:right;" | 459
| holding
| u16
| -
| Fan start delay (dead band)
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01CD
| style="text-align:right;" | 461
| holding
| u16
| -
| Fan stop delay (dead band)
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01C0
| style="text-align:right;" | 448
| holding
| u16
| A18
| Liquid level alarm delay
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01C8
| style="text-align:right;" | 456
| holding
| u16
| -
| Minimum fan speed
| %
| style="text-align:right;" | 0
| style="text-align:right;" | 100
|-
| 0x01C2
| style="text-align:right;" | 450
| holding
| u16
| /07
| Number of compressors on in circuit 1 with probe damaged
|
| style="text-align:right;" | 0
| style="text-align:right;" | 4
|-
| 0x01C1
| style="text-align:right;" | 449
| holding
| u16
| /08
| Number of compressors on in circuit 2 with probe damaged
|
| style="text-align:right;" | 0
| style="text-align:right;" | 2
|-
| 0x01C4
| style="text-align:right;" | 452
| holding
| u16
| /12
| Number of fans on with probe damaged
|
| style="text-align:right;" | 0
| style="text-align:right;" | 4
|-
| 0x01D5
| style="text-align:right;" | 469
| input
| u16
| -
| Version of the application
|
| style="text-align:right;" |
| style="text-align:right;" |
|-
| 0x01D9
| style="text-align:right;" | 473
| holding
| u16
| /35
| Type of refrigerant
|
| style="text-align:right;" | 0
| style="text-align:right;" | 11
|-
| 0x01D6
| style="text-align:right;" | 470
| holding
| u16
| /03
| Capacity of compressor 1
|
| style="text-align:right;" | 0
| style="text-align:right;" | 500
|-
| 0x01D3
| style="text-align:right;" | 467
| holding
| u16
| /04
| Capacity of compressor 2
|
| style="text-align:right;" | 0
| style="text-align:right;" | 500
|-
| 0x01DC
| style="text-align:right;" | 476
| holding
| u16
| /05
| Capacity of compressor 3
|
| style="text-align:right;" | 0
| style="text-align:right;" | 500
|-
| 0x01DA
| style="text-align:right;" | 474
| holding
| u16
| /06
| Capacity of compressor 4
|
| style="text-align:right;" | 0
| style="text-align:right;" | 500
|-
| 0x01DE
| style="text-align:right;" | 478
| input
| u16
| /11
| Inverter readout %
| %
| style="text-align:right;" | 0
| style="text-align:right;" | 100
|-
| 0x01DF
| style="text-align:right;" | 479
| holding
| u16
| /15
| Multifunction DI configuration
|
| style="text-align:right;" | 0
| style="text-align:right;" | 12
|-
| 0x01D7
| style="text-align:right;" | 471
| holding
| u16
| /16
| Type of discharge probe
|
| style="text-align:right;" | 0
| style="text-align:right;" | 2
|-
| 0x01DB
| style="text-align:right;" | 475
| holding
| u16
| /21
| Type of probe B2
|
| style="text-align:right;" | 0
| style="text-align:right;" | 2
|-
| 0x01DD
| style="text-align:right;" | 477
| holding
| u16
| /22
| Type of probe B3
|
| style="text-align:right;" | 0
| style="text-align:right;" | 2
|-
| 0x01D0
| style="text-align:right;" | 464
| holding
| u16
| /37
| Delay restart after black out
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01D8
| style="text-align:right;" | 472
| holding
| u16
| C04
| Min time between two stop calls for different compressors
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01D2
| style="text-align:right;" | 466
| holding
| u16
| C06
| Time between compressor stop call with Prevent function
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01D1
| style="text-align:right;" | 465
| holding
| u16
| C07
| Operating hour threshold for maintenance
| h x10
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01D4
| style="text-align:right;" | 468
| input
| u16
| C08
| Compressor 1 hours
| h x10
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01E5
| style="text-align:right;" | 485
| input
| u16
| C10
| Compressor 2 hours
| h x10
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01E9
| style="text-align:right;" | 489
| input
| u16
| C12
| Compressor 3 hours
| h x10
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01E6
| style="text-align:right;" | 486
| input
| u16
| C14
| Compressor 4 hours
| h x10
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01E3
| style="text-align:right;" | 483
| holding
| u16
| r05
| Type of compressor rotation
|
| style="text-align:right;" | 0
| style="text-align:right;" | 2
|-
| 0x01EC
| style="text-align:right;" | 492
| holding
| u16
| r06
| Type of compressor control
|
| style="text-align:right;" | 0
| style="text-align:right;" | 2
|-
| 0x01EA
| style="text-align:right;" | 490
| holding
| u16
| r08
| Maximum call for compressor starts in dead band by time
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01EE
| style="text-align:right;" | 494
| holding
| u16
| r10
| Maximum call for compressor stops in dead band by time
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01EF
| style="text-align:right;" | 495
| holding
| u16
| r20
| Type of fan rotation
|
| style="text-align:right;" | 0
| style="text-align:right;" | 1
|-
| 0x01E7
| style="text-align:right;" | 487
| holding
| u16
| r21
| Type of fan control
|
| style="text-align:right;" | 0
| style="text-align:right;" | 2
|-
| 0x01EB
| style="text-align:right;" | 491
| holding
| u16
| r22
| Integral time for P+I fan control
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01ED
| style="text-align:right;" | 493
| holding
| u16
| r23
| Time between 2 fans starts in dead band
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01E0
| style="text-align:right;" | 480
| holding
| u16
| r24
| Time between 2 fans stops in dead band
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01E8
| style="text-align:right;" | 488
| holding
| u16
| r27
| Inverter speed up time
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01E2
| style="text-align:right;" | 482
| holding
| u16
| r28
| Inverter ramp up time
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01E1
| style="text-align:right;" | 481
| holding
| u16
| r29
| Minimum inverter output
| %
| style="text-align:right;" | 0
| style="text-align:right;" | 100
|-
| 0x01E4
| style="text-align:right;" | 484
| holding
| u16
| r30
| Maximum inverter output
| %
| style="text-align:right;" | 0
| style="text-align:right;" | 100
|-
| 0x01F5
| style="text-align:right;" | 501
| holding
| u16
| r31
| Triac impulse duration
| ms
| style="text-align:right;" | 0
| style="text-align:right;" | 10
|-
| 0x01F9
| style="text-align:right;" | 505
| holding
| u16
| A02
| High suction pressure 1 alarm delay
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01F6
| style="text-align:right;" | 502
| holding
| u16
| A04
| Low suction pressure 1 alarm delay
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01F3
| style="text-align:right;" | 499
| holding
| u16
| A06
| High suction pressure 2 alarm delay
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01FC
| style="text-align:right;" | 508
| holding
| u16
| A08
| Low suction pressure 2 alarm delay
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01FA
| style="text-align:right;" | 506
| holding
| u16
| A11
| Low discharge pressure alarm delay
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01FE
| style="text-align:right;" | 510
| holding
| u16
| A12
| Compressor thermal overload alarm delay
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01FF
| style="text-align:right;" | 511
| holding
| u16
| A13
| Prevent time in which no compressor starts are enabled
| m
| style="text-align:right;" | 0
| style="text-align:right;" | 99
|-
| 0x01F7
| style="text-align:right;" | 503
| holding
| u16
| A14
| Prevent time in which the activation signals the alarm
| m
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01FB
| style="text-align:right;" | 507
| holding
| u16
| A15
| Time to reset prevent alarm
| m
| style="text-align:right;" | 0
| style="text-align:right;" | 99
|-
| 0x01FD
| style="text-align:right;" | 509
| holding
| u16
| A20
| Alarm signal delay
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01F0
| style="text-align:right;" | 496
| holding
| u16
| A21
| Time to change low pressure alarm from automatic to manual
| s
| style="text-align:right;" | 0
| style="text-align:right;" | 999
|-
| 0x01F1
| style="text-align:right;" | 497
| input
| u16
|
| Operating percentage of first capacity controlled compressor
|
| style="text-align:right;" |
| style="text-align:right;" |
|-
| 0x01F4
| style="text-align:right;" | 500
| input
| u16
|
| Operating percentage of second capacity controlled compressor
|
| style="text-align:right;" |
| style="text-align:right;" |
|-
|}