Register/ address Type Read/ write Default Format Purpose Versions

insertions

6 input R 0x7FFF °C × 16 (signed) Temperature with built-in 1-Wire sensor
7 input R 0x7FFF °C × 16 (signed) Temperature from external 1-Wire sensor
110 holding RW 96 baud rate / 100 RS-485 port speed, "'divided by 100"'. Permissible speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 >3.1.0
111 holding RW 0 configure the RS-485 port parity bit. Valid values: 0 - no parity bit (none), 1 - odd (odd), 2 - even (even)
112 holding RW 2 number of stop bits of RS-485 port. Valid values: 1, 2
120 (0x78) holding RW 0 other than 0 write to the register causes a reset of the module without saving state
121 (0x79) input R - mV current supply voltage of the module
128 (0x80) holding RW 1 The Modbus address of the device
200-206 input R see device Signature signature
220-241 input R __date__ _ _ time__ the build date of the firmware
250-269 input R string, null-terminated firmware version
270-271 input R 32-bit unsigned int unique identifier (S/N)