12 063
правки
(Новая страница: «Permissible current: up to 3A per channel.») |
(Новая страница: «400px|thumb|none|Connection scheme») |
||
(не показано 8 промежуточных версий этого же участника) | |||
Строка 11: | Строка 11: | ||
Permissible current: up to 3A per channel. | Permissible current: up to 3A per channel. | ||
Our detailed article in russian on habr.com about the choice of relay parameters for the switched load: https://habr.com/ru/company/wirenboard/blog/422197/ | |||
{| class="wikitable" | {| class="wikitable" | ||
! | !Parameter | ||
! colspan="2" | | ! colspan="2" |Value | ||
|- | |- | ||
| | |Number of outputs | ||
| colspan="2" |8 | | colspan="2" |8 | ||
|- | |- | ||
| | |Output type | ||
| colspan="2" | | | colspan="2" |mechanical relay | ||
|- | |- | ||
| rowspan="2" | | | rowspan="2" |contact Configuration | ||
|K2-K7 | |K2-K7 | ||
|SPST, | |SPST, normally open | ||
states: | |||
* | * off | ||
* | * C is closed and NO | ||
|- | |- | ||
|K1, K8 | |K1, K8 | ||
|SPDT ( | |SPDT (contacts K, NO, NC) | ||
conditions: | |||
* | * C and NS closed | ||
* | * C and NO closed | ||
|- | |- | ||
| | |Maximum switching voltage, alternating current | ||
| colspan="2" |250 | | colspan="2" |250 V | ||
|- | |- | ||
| | |Maximum switching voltage, direct current | ||
| colspan="2" |30 | | colspan="2" |30 V | ||
|- | |- | ||
| | |Maximum switching current, per channel (*) | ||
| colspan="2" |3 | | colspan="2" |3 A | ||
|- | |- | ||
| | |The channel resistance in the open state | ||
| colspan="2" |< 100 | | colspan="2" |< 100 megohms | ||
|- | |- | ||
| | |Voltage isolation between the controller and the output | ||
| colspan="2" |1500 | | colspan="2" |1500 V (RMS.) | ||
|- | |- | ||
| | |Lifetime: number of switches | ||
for 10 A 230 V AC load, cos φ = 1 | |||
| colspan="2" |100 000 | | colspan="2" |100 000 | ||
|- | |- | ||
| | |Module type | ||
| colspan="2" |"O" (non-inverted address scheme) | | colspan="2" |"O" (non-inverted address scheme) | ||
|- | |- | ||
| | |Maximum power consumption | ||
| colspan="2" | | | colspan="2" |1W | ||
|- | |- | ||
| | |Width, DIN units | ||
| colspan="2" |3 | | colspan="2" |3 | ||
|- | |- | ||
| | |Size | ||
| colspan="2" |53,3x90,2x57,5 | | colspan="2" |53,3x90,2x57,5 mm | ||
|} | |} | ||
<nowiki>*</nowiki>) | <nowiki>*</nowiki>) Maximum switching current is specified for 230 VAC resistive load. | ||
[[File:DIN 3U.png |300px|thumb|right| | [[File:DIN 3U.png |300px|thumb|right|Dimensions]] | ||
== | == Connection to the controller == | ||
See [[Модули ввода-вывода/en#Activating the modules in the controller web interface|Activating the modules in the web interface of the controller]]. In the Module type field, select '''WBIO-DO-RxA-8: 8 Channel Relay I/O module'''. In the web interface the relay will be presented by the controls of EXT'''x'''_R3A1 — EXT'''x'''_R3A8 of the Discrete I/O devices. The corresponding MQTT-topics: /devices/wb-gpio/controls/EXT'''x'''_R3A'''y'''. | |||
[[File:Wbio-do-rxa-8_controls.png|300px|thumb|right| | [[File:Wbio-do-rxa-8_controls.png|300px|thumb|right|Controls of the module in the web interface]] | ||
== | == Load connection== | ||
Relays are connected in a phase break. | |||
[[Файл:Relay outputs.png|400px|thumb|none| | [[Файл:Relay outputs.png|400px|thumb|none|Connection scheme]] |
правки