12 063
правки
(Новая страница: «To enter the leakage sensor (input 1) use the mode 1000 (8) — turn on when the circuit. frameless|270px<br> To enter the reset button (inpu…») |
(Новая страница: «Leaving input 1 closed, turn off and turn on the relay power: after 20 minutes, relays 1, 2 and 3 will turn on again.») |
||
(не показаны 2 промежуточные версии этого же участника) | |||
Строка 224: | Строка 224: | ||
To enter the leakage sensor (input 1) use the mode 1000 (8) — turn on when the circuit. [[File:Mm_1000.png|frameless|270px]]<br> To enter the reset button (input 2) use mode 0100 (4) — turn off when closing. [[File:Mm_0100.png|frameless|270px]]<br> | To enter the leakage sensor (input 1) use the mode 1000 (8) — turn on when the circuit. [[File:Mm_1000.png|frameless|270px]]<br> To enter the reset button (input 2) use mode 0100 (4) — turn off when closing. [[File:Mm_0100.png|frameless|270px]]<br> | ||
On the map mapping-registers we determine that to enter 1, you need to write the value 8 in the registers 384, 385, 386, and to enter 2 — write the value 4 in the registers 392, 393, 394: | |||
<syntaxhighlight lang="bash">modbus_client --debug -mrtu -pnone -s2 /dev/ttyRS485-1 -a1 -t0x10 -r384 8 8 8</syntaxhighlight> | <syntaxhighlight lang="bash">modbus_client --debug -mrtu -pnone -s2 /dev/ttyRS485-1 -a1 -t0x10 -r384 8 8 8</syntaxhighlight> | ||
Строка 230: | Строка 230: | ||
Checking: close input 1 and iGND and leave it closed. Relays 1, 2 and 3 must be switched on. Then we close and open the input 2 — all three relay relays are off. Wait 20 minutes. Since input 1 remains closed (leakage is not eliminated), relays 1, 2 and 3 will switch back on after 20 minutes. | |||
Leaving input 1 closed, turn off and turn on the relay power: after 20 minutes, relays 1, 2 and 3 will turn on again. |
правки