12 063
правки
(Новая страница: «==== Bus parameters. ====») |
|||
(не показано 9 промежуточных версий этого же участника) | |||
Строка 1: | Строка 1: | ||
<languages/> | <languages/> | ||
[[File:MCM16.JPG| | [[File:MCM16.JPG|альт=WB-MCM16 module|мини|414x414pcs|WB-MCM16 Module]] | ||
[[File:WB-MCM16 | [[File:Модуль WB-MCM16.png|альт=WB-MCM16 Module|мини|414х414пкс|WB-MCM16 Module, push terminals]] | ||
The model is discontinued. Recommended replacement - [[WB- | The model is discontinued. Recommended replacement - [[WB-MCM8_Модуль_счетных_входов_8-канальный/en|WB-MCM8]]. '''[https://wirenboard.com/en/product/WB-MCM8/ Buy WB-MCM8 in the online store]''' | ||
{{#vardefine:ProductFullName1| 16-channel pulse counting module WB-MCM16}} {{#vardefine:FileName1|WB-MCM16}} {{#vardefine:ProductName1|WB-MCM16}} | {{#vardefine:ProductFullName1| 16-channel pulse counting module WB-MCM16}} {{#vardefine:FileName1|WB-MCM16}} {{#vardefine:ProductName1|WB-MCM16}} | ||
Строка 60: | Строка 60: | ||
==== Bus parameters. ==== | ==== Bus parameters. ==== | ||
Speed 9600 bit/s, data - 8 bit, | |||
parity – no, stop bit - 2. | |||
=== | === Modbus commands supported by the device === | ||
Строка 78: | Строка 78: | ||
|- | |- | ||
| | |READ_HOLDING_REGISTERS || 4 | ||
|- | |- | ||
Строка 93: | Строка 93: | ||
|} | |} | ||
Address change is broadcast (slave_id 0) team record (WRITE_SINGLE_REGISTER) to holding register with address 128 (0x80). | |||
The address 200 has a 6-byte signature. The signature is unique for each device model and allows you to identify the model. | |||
To obtain the signatures necessary to fulfill READ_HOLDING_REGISTERS address 200 length 6. | |||
Writing to this area of memory is not supported and error 3 is returned when attempting to write to an invalid location. | |||
== | == Register map == | ||
правки