Translations:WB-MSW v.3 Modbus Sensor/31/en: различия между версиями
(Новая страница: «==== How to open the sensor housing ==== {| border="1" cellpadding="2" cellspacing="1" | 450px|thumb|center| || File:WB-MSW3-OPEN_2…») |
FuzzyBot (обсуждение | вклад) м (FuzzyBot переименовал страницу Translations:WB-MSW v.3/31/en в Translations:WB-MSW v.3 Modbus Sensor/31/en без оставления перенаправления: Часть переводимой страницы WB-MSW v.3.) |
Текущая версия на 21:04, 20 апреля 2021
How to open the sensor housing
Locate the latch tab on the underside of the sensor housing. | Push the screwdriver against the tab perpendicular to the side of the sensor housing until it stops. | Lift the top cover of the sensor. |
Th and VOC modules
Temperature/humidity (TH) and VOC measurement are done on separate modules. Modules are installed on the arrow in the connectors. For more accurate measurement, the TH module must be installed in the upper left connector. Otherwise it is heated by the CO2 sensor and overestimates the reading by 1-2 degrees.