Строка 123: | Строка 123: | ||
{| class="wikitable" style="text-align:center" | {| class="wikitable" style="text-align:center" | ||
|[[ | |[[File:Ai-dv-12-add_list_of_channels.png|400px|thumb|right|Add channel list]] | ||
|[[ | |[[File:Ai-dv-12-only-scale.png|400px|thumb|left|Leave only the scale]] | ||
|[[ | |[[File:Ai-dv-12-DIFF1_right_scale.png|600px|thumb|right|Set the channel name and conversion factor]] | ||
|} | |} | ||
Строка 131: | Строка 131: | ||
{| class="wikitable" style="text-align:center" | {| class="wikitable" style="text-align:center" | ||
|+ | |+ Dependence of the input operation mode on the installed jumper and scaling factor | ||
!''' | !'''The presence of the jumper'''!! '''Entry type'''!! '''Mode''' || '''Value scale''' | ||
|- | |- | ||
|rowspan="2"|''' | |rowspan="2"|'''No''' | ||
| | |Unipolar | ||
| | |Input voltage 0 — 2.5 V | ||
|0.01 | |0.01 | ||
|- | |- | ||
| | |Differential | ||
| | |Input voltage ±400 mV | ||
|0.01 | |0.01 | ||
|- | |- | ||
|rowspan="2"|''' | |rowspan="2"|'''Is''' | ||
|- | |- | ||
| | |Differential | ||
| | |Input voltage ±50 V | ||
|0.2126 | |0.2126 | ||
|} | |} | ||
For models designed to measure current, the '''scale' ''factor must be set to 0.1 | |||
-- | -- | ||
== | ==Device pictures and drawings == | ||
{{Wbincludes:WBPicturesNoDrawing|2}} | {{Wbincludes:WBPicturesNoDrawing|2}} | ||
== | == Bugs and features == | ||
=== ERRAIDV01: | === ERRAIDV01: Reduced precision of inputs === | ||
==== | ==== Affected devices ==== | ||
WBIO-AI-DV-12/4-20MA | WBIO-AI-DV-12/4-20MA shipped before May 20, 2019. | ||
==== | ====Description==== | ||
Current measurement error in WBIO-AI-DV-12/4-20MA can be up to 1%. | |||
==== | ====Reasons and detailed description==== | ||
The nominal value of the input protective resistor is selected too large relative to the internal resistance of the ADC. | |||
==== | ====Workarounds==== | ||
no | |||
==== | ====Scheduled fix=== | ||
Starting from May 20,2019 components, providing the error is not more than 0.1%+0.003 mA, are installed in WBIO-AI-DV-12/4-20MA |