WBE-DI-DR-3/en: различия между версиями
Fizikdaos (обсуждение | вклад) |
|||
Строка 5: | Строка 5: | ||
[[Файл:EXT1.jpeg|thumb|300px|Extension Module WBE-DI-DR-3]] | [[Файл:EXT1.jpeg|thumb|300px|Extension Module WBE-DI-DR-3]] | ||
The module for connection of sensors, counters to the outputs of the type [[ | The module for connection of sensors, counters to the outputs of the type [["Сухой контакт"/en|Dry contact]] or open collector. | ||
State of logic low: input in air. | State of logic low: input in air. |
Текущая версия на 19:17, 1 июля 2019
Extension Module, 3 digital inputs
The module for connection of sensors, counters to the outputs of the type Dry contact or open collector.
State of logic low: input in air.
State of logical high: input is connected to ground (GND) of the controller. It allowed to connect either directly or through the resistance less than 300 ohms.
Installed in slot MOD-1 or MOD-2 controller Wiren Board 5.
Three channels.
Pinout:
Terminal | Function |
---|---|
O1 | Input 1 |
O2 | Input 2 |
O3 | Input 3 |
GPIO
When installed in first slot MOD-1
Input | GPIO |
---|---|
O1 | 85 |
O2 | 76 |
O3 | 91 |
When installed in second slot MOD-2
Input | GPIO |
---|---|
O1 | 22 |
O2 | 23 |
O3 | 83 |