Purpose
The device is designed for tasks that require monitoring of currents and voltages in DC networks, for example for technical metering of electricity.
The device directly measures the voltage and current in the load. The values obtained are used to calculate power (kW) and energy (kWh).
Technical specifications
Contains 4 inputs for Hall sensors for load current measurement and 1 (2) input for voltage measurement.
Parameter | Value |
---|---|
voltage measuring Inputs | |
Number of inputs | 2 (single-ended) |
1 (differential) | |
Input type | voltage measurement,
uninsulated |
Measured voltage | 48V DC (0-70V) |
Allowable voltage | -70V ... +70V DC |
Input impedance | 10 kOhm |
current measuring Inputs | |
Number of inputs | 4 |
Input type | connecting hall sensors |
Sensor type | open-loop,
5V power supply, output 2.5 V +/- 0.625 V (FS) |
Allowable voltage | -5V .. +5V |
Power output for hall sensors | 5V, common to all sensors
with short circuit protection |
Other | |
Module type | "I" (inverted address scheme) |
Maximum power consumption | 0.1 W |
Width, DIN units | 2 |
Size | 36,3x90,2x57,5 mm |