== 3A Relay Output Module (WBIO-DO-R3A-8) ==
Версия от 15:25, 15 июля 2019; RomanKulibaba (обсуждение | вклад) (Новая страница: «300px|thumb|right|Dimensions»)
Purpose
Control of contactors, warning lights, etc.
Technical specifications
Contains 8 relays. Two of them are rocker (NO/COM/NC) switching corresponding 8 outputs. The outputs are output to screw clamps designed for a maximum current of 20 A.
Permissible current: up to 3A per channel.
Our detailed article in russian on habr.com about the choice of relay parameters for the switched load: https://habr.com/ru/company/wirenboard/blog/422197/
Parameter | Value | |
---|---|---|
Number of outputs | 8 | |
Output type | mechanical relay | |
contact Configuration | K2-K7 | SPST, normally open
states:
|
K1, K8 | SPDT (contacts K, NO, NC)
conditions:
| |
Maximum switching voltage, alternating current | 250 V | |
Maximum switching voltage, direct current | 30 V | |
Maximum switching current, per channel (*) | 3 A | |
The channel resistance in the open state | < 100 megohms | |
Voltage isolation between the controller and the output | 1500 V (RMS.) | |
Lifetime: number of switches
for 10 A 230 V AC load, cos φ = 1 |
100 000 | |
Module type | "O" (non-inverted address scheme) | |
Maximum power consumption | 1W | |
Width, DIN units | 3 | |
Size | 53,3x90,2x57,5 mm |
*) Maximum switching current is specified for 230 VAC resistive load.
Подключение к контроллеру
Смотрите раздел Активирование в веб-интерфейсе контроллера. В поле "Module type" следует выбрать устройство WBIO-DO-RxA-8: 8 Channel Relay I/O module. В веб-интерфейсе реле будут представлены контролами EXTx_R3A1 — EXTx_R3A8 устройства Discrete I/O. Соответствующие MQTT-топики: /devices/wb-gpio/controls/EXTx_R3Ay.
Подключение нагрузки
Реле подключаются в разрыв фазы.