Input-output modules
IO modules are joined to the connector on the side WB5.
You can connect up to 8 modules: Up to 4 input modules (type I), and up to 4 output module (Type O and IO). WB5 automatically detects connected module and its type. Addresses are distributed sequentially. Connect up to 4 modules can be in any order. When a larger number should be connected first one type, then the other.
Communication Interface - I2C.
Digital Input Module type "dry contact" (WBIO-DI-DR-8)
Contains 8 inputs for connecting "dry contacts" with the group galvanic isolation. The circuit inputs shown in Fig. On input is applied ~ 4.5V, ground fault current flows small (1mA), triggering input.
To input trigger pulse width must be at least 10 ms ???. The time between pulses - 5ms
Digital Output Module (WBIO-DO-HS-8)
Contains 8 outputs such as "High Side Switch" - when you turn on channel Vin voltage is supplied to the output.
Designed to control relays, low-voltage motors, etc.
Current up to 0,6A per channel. Built-in overvoltage protection (including load dump), overheat and short circuit protection.
Requires external power supply to the terminals 'Vin' and 'GND' .
Ground module must be connected with the ground controller!
Power supply from 11 to 45V.
Relay Output Module (WBIO-DO-R3A-8)
Contains 8 relays. Two of them are flip (NO / COM / NC).
Current up to 10A per channel NO-NC (on / off), up to 3A channels SPDT relay. Protection from arcing contacts.
Rated current is specified for resistive loads 230V AC.
Модуль ввода-вывода с TTL-уровнями (WBIO-DIO-TTL-8)
Содержит 8 каналов ввода-вывода с уровнями напряжения 5В,каналы по умолчанию настроены как "выход". Ток до 20 ма. Защита перенапряжений до 60В.
Мезонинный модуль ввода-вывода с TTL-уровнями (WBMZ-DIO-TTL-16)
Основная статья: WBMZ-DIO-TTL-16.