Register/ address | Type | Read/ write | Default | Format | Purpose | Versions
insertions |
---|---|---|---|---|---|---|
6 | input | R | 0x7FFF | °C × 16 (signed) | Temperature with built-in 1-Wire sensor | |
7 | input | R | 0x7FFF | °C × 16 (signed) | Temperature from external 1-Wire sensor | |
110 | holding | RW | 96 | baud rate / 100 | RS-485 port speed, "'divided by 100"'. Permissible speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 | >3.1.0 |
111 | holding | RW | 0 | configure the RS-485 port parity bit. Valid values: 0 - no parity bit (none), 1 - odd (odd), 2 - even (even) | ||
112 | holding | RW | 2 | number of stop bits of RS-485 port. Valid values: 1, 2 | ||
120 (0x78) | holding | RW | 0 | other than 0 | write to the register causes a reset of the module without saving state | |
121 (0x79) | input | R | - | mV | current supply voltage of the module | |
128 (0x80) | holding | RW | 1 | The Modbus address of the device | ||
200-206 | input | R | see device Signature | signature | ||
220-241 | input | R | __date__ _ _ time__ | the build date of the firmware | ||
250-269 | input | R | string, null-terminated | firmware version | ||
270-271 | input | R | 32-bit unsigned int | unique identifier (S/N) |