Register/ address Type Read/ write Default Format Purpose Versions

insertions

6 input R 0x7FFF °C × 16 (signed) Temperature with built-in sensor
7 input R 0x7FFF °C × 16 (signed) Temperature from the first external 1-Wire sensor
8 input R 0x7FFF °C × 16 (signed) Temperature from second external 1-Wire sensor
20 input R 0 °C × 16 (signed) Temperature from the first external 1-Wire sensor. In case of an error, the sensor retains the previous valid value (sensor status read from the discrete register 16). starting with firmware 4.6.0
21 input R 0 °C × 16 (signed) Temperature from the second external 1-Wire sensor. In case of an error, the sensor retains the previous valid value (sensor status read from the discrete register 17).
99 holding RW 16 1 = 0.0625 C (available from firmware version 3.10.0)

Suspicious value filter for 1-Wire sensors (85.000 C, 127.937 C). Values are discarded if the previous value differs from the suspect value by more than * 0.0625 C. Write 0 to disable the filter.