The LRADC channel of the processor that the Wiren Board uses to operate the ADC has an integrated current source. This allows to measure the resistance of the load connected to the outputs of the ADC, i.e., to read values of resistive sensors. | The LRADC channel of the processor that the Wiren Board uses to operate the ADC has an integrated current source. This allows to measure the resistance of the load connected to the outputs of the ADC, i.e., to read values of resistive sensors. | ||
See also the description in the documentation | See also the description in the processor documentation, p. 1334 -[http://www.freescale.com/files/dsp/doc/ref_manual/IMX23RM.pdf Reference Manual] | ||
Resistance measurement is implemented in the wb-homa-adc driver, see [[ADC/en |ADC]]. | Resistance measurement is implemented in the wb-homa-adc driver, see [[ADC/en |ADC]]. | ||
Строка 10: | Строка 10: | ||
== The measuring procedure in the manual mode == | == The measuring procedure in the manual mode == | ||
Make sure the wb-homa-adc daemon is not running | |||
=== | === Disable output === | ||
( | (only for Wiren Board rev. 2.8) | ||
* | * For terminals 2-7: close the transistor. See [[Список GPIO/en|List of GPIOs]], [[Управление низковольтной нагрузкой/en|Low voltage load management]]. | ||
* | * For terminal strip 9: set GPIO 2 to input mode ([[Работа с GPIO/en|Managing GPIO]]) | ||
=== | === Channel selection === | ||
Use wb-adc-set-mux to select a channel([[ADC/en|ADC]]) | |||
=== | === Setting output current === | ||
Setting the output current is not supported by the driver, so it is implemented using the userspace application with direct memory access. | |||
Command <b>lradc-set-current</b> (https://github.com/contactless/wirenboard/tree/master/utils/adc/resistance). | |||
<pre> | <pre> | ||
Строка 38: | Строка 38: | ||
</pre> | </pre> | ||
The maximum current is 300 µa. The current is set in increments of 20 µa. | |||
Setting 100 µa current: | |||
<pre> | <pre> | ||
Строка 46: | Строка 46: | ||
</pre> | </pre> | ||
Disconnecting the current source: | |||
<pre> | <pre> | ||
root@wirenboard:~# lradc-set-current off | root@wirenboard:~# lradc-set-current off | ||
</pre> | </pre> | ||
It is necessary to set the maximum possible value of the output current at which the voltage on the LRADC does not exceed 1.85 V, i.e. the raw result is not equal to 4095. | |||
In the following example 40 µa is the optimum current: | |||
<pre> | <pre> | ||
Строка 71: | Строка 71: | ||
=== | === Calculating the results === | ||
The resistance is calculated by the formula: | |||
<pre> | <pre> | ||
Строка 79: | Строка 79: | ||
</pre> | </pre> | ||
<b>r</b> | <b>r</b> is the measured resistance, <b>R2</b> is the series resistance of the channel | ||
<b>R1</b> | <b>R1</b> is parallel resistance (divider arm/leakage currents). | ||
<b> V </b> | <b> V </b> is input voltage LRADC measured by the processor: | ||
<pre> | <pre> | ||
Строка 89: | Строка 89: | ||
</pre> | </pre> | ||
where N is the raw LRADC readings, I is the output current. | |||
For different versions: | |||
* Wiren Board 5 ( | * Wiren Board 5 (terminals R1-R2): <b>R2 = 3150 Ohm, R1 = 1000kOhm</b>. | ||
* Wiren Board 4 ( | * Wiren Board 4 (terminals R1-R2): <b>R2 = 3570 Ohm, R1 = 120kOhm</b>. | ||
* Wiren Board Smart Home rev. 3.5 ( | * Wiren Board Smart Home rev. 3.5 (terminals R1-R4): <b>R2 = 600 Ohm, R1 = 93kOhm</b>. | ||
* Wiren Board rev. 2.8. <b>R2 = 12kOhm, R1 = 33.0 kOhm</b>. | * Wiren Board rev. 2.8. <b>R2 = 12kOhm, R1 = 33.0 kOhm</b>. |