Firmware Changelog: различия между версиями
Метка: visualeditor |
Kilpio (обсуждение | вклад) |
||
Строка 5: | Строка 5: | ||
!Affected devices | !Affected devices | ||
!Changelog | !Changelog | ||
|- | |||
|WB-MDM2 | |||
|1.1.0 | |||
| WB-MD2 | |||
| Two modbus holding registers 65 and 66 were added for users can choose 1 of 3 dimming curves: (0)incandecent bulbs, (1)LED bulbs, (2)resistive load | |||
|- | |- | ||
|WB-MS | |WB-MS |
Версия 16:08, 24 мая 2018
Общая таблица по всем устройствам
Source project | Version | Affected devices | Changelog |
---|---|---|---|
WB-MDM2 | 1.1.0 | WB-MD2 | Two modbus holding registers 65 and 66 were added for users can choose 1 of 3 dimming curves: (0)incandecent bulbs, (1)LED bulbs, (2)resistive load |
WB-MS | 3.10.1 | WB-MS, WB-M1W2, WB-MIR | 1-wire reset time changed from ~410 us to ~550 us. As in 1-Wire Standard, should be between 480 and 640 us |
WB-MS | 3.10.0 | WB-MS, WB-M1W2, WB-MIR | added filter out algorithm for suspicious values 85C and 127.937C from 1-wire temperature sensors |