Firmware Changelog
Версия от 14:07, 10 июля 2018; EvgenyBoger (обсуждение | вклад)
Общая таблица по всем устройствам
Source project | Version | Affected devices | Changelog |
---|---|---|---|
WB-MDM2 | 1.1.0 | WB-MD2 | Two modbus holding registers 65 and 66 were added for users can choose 1 of 3 dimming curves: (0)incandecent bulbs, (1)LED bulbs, (2)resistive load |
WB-MS | 3.10.1 | WB-MS, WB-M1W2, WB-MIR | 1-wire reset time changed from ~410 us to ~550 us. As in 1-Wire Standard, should be between 480 and 640 us |
WB-MS | 3.10.0 | WB-MS, WB-M1W2, WB-MIR | added filter out algorithm for suspicious values 85C and 127.937C from 1-wire temperature sensors |