Starting address Quantity Purpose In modifications From firmware version
0 1 Enable buzzer (buzzer) WB-MSW2, WB-v MSW.3
1 1 Forced calibration of the built-in CO2 sensor. Turn on after 20 minutes of operation at a CO2 level of 400 ppm WB-MSW2
2 1 Turn on the heating (heater) in the temperature and humidity sensor chip HDC1080 WB-MS (in the 2017 series), WB-MSW2, WB-MSW V. 3 3.2.0
3 1 The inclusion of a CO2 sensor WB-MSW V. 3 4.1.0
10 1 Green led on WB-MSW V. 3
11 1 Enable red led WB-v MSW.3