Translations:Sensors Modbus Management/7/en
Версия от 22:38, 29 марта 2020; EvgenyBoger (обсуждение | вклад)
Register/ address | Type | Read/ write | default or error Value | Format | Purpose | Supported in | From version
insertions | ||||
---|---|---|---|---|---|---|---|---|---|---|---|
WB-MS (model code) | WB-MS v2 (model code) | WB-MSW | WB-MSW2 | WB-MSW V. 3 | |||||||
0 | input | R | 0x7FFF | °C × 10 (signed) | Temperature with built-in sensor | T | - | - | + | + | |
1 | input | R |
|
relative humidity with built-in sensor | H | - | + | + | + | ||
2 | input | R | - | LC | "(register is not used in WB-MSW sensors, registers 9 and 10 instead)" Illumination from built-in sensor |
L | Lux | - | - | - | |
3 | input | R | - | dB × 100 | Noise level multiplied by 100 | S | - | + | S | S | |
4 | input | R | 0x7FFF | °C × 100 (signed) | Temperature with built-in sensor | + | + | - | - | + | 4.2 |
5 | input | R | - | %RH × 100 (signed) | Relative humidity with built-in sensor | + | + | - | - | + | 4.2 |
6 | input | R | 0x7FFF | °C × 16 (signed) | Temperature from external sensor | D | + | - | - | - | |
7 | input | R | 0x7FFF | °C × 16 (signed) | Temperature from external sensor | D | + | - | - | - | |
8 | input | R | 0xFFFF | PPM | CO2 concentration | - | - | After | C | ||
9-10 | input | R | LC | The illumination, multiplied by 100 (9 - high-order, 10 — LSB luminance values) | - | - | + | L | |||
11 | input | R | 0xFFFF | PPM | Air quality | - | VOC | - | - | + | |
88 | holding | RW | 0 | ppm (400-1500) | Service register, doesn't present in most devices. Manual calibration of CO2 sensor. For calibration, write down here the current CO2 concentration measured by another instrument | - | - | - | C | C | 3.12 |
89 | holding | RW | 0xFF | days' | Service register, doesn't present in most devices. Cycle time for co sensor self-calibration algorithm (ABC) | - | - | - | C | C | 3.12 |
90 | holding | RW | 20 (200 ms) | × 10 ms | light averaging Time |
|
- | - | - | - | |
91 | holding | RW | 20 (200 ms) | × 10 ms | Noise averaging time | S | - | + | S | S | |
95 | holding | RW | 1 | 1 or 0 | CO2 sensor (ABC) auto-calibration to atmospheric CO2 | - | - | - | After | C | |
96 | holding | R | 2000 / 5000 | ppm | (available from firmware version 3.5.0) CO2 concentration measurement Range. Valid values: 2000, 5000, 10000. | - | - | - | C | C | 3.5.0 |