== | == Connection of sensors and counters with pulse outputs and buttons to the Wiren Board 5 == | ||
[[Wiren_Board_5: | [[Wiren_Board_5:hardware Part#Universal inputs/outputs A1-A4|Universal inputs/outputs A1-A4]] of the controller can be used to connect various devices with pulse output or buttons. A typical example is water meters or electricity meters. | ||
=== | ==== Connection ==== | ||
Pulse input one wire is connected to the power supply 5 — 24 V, the second wire to the terminal A1. | |||
[[File:Installation_WB5_+_WaterMeter.png|thumb|center|400px| | [[File:Installation_WB5_+_WaterMeter.png|thumb|center|400px|Example of connecting a meter with a pulse output]] | ||
Next, in the web interface, you must configure universal input A1 as a counter. | |||
In the '''Configs''' menu, select '''GPIO Driver Configuration'''. | |||
On the panel choose A1_IN login settings, click '''Properties''' and mark all the checkboxes. Then click '''Properties''' again. | |||
Now there are additional fields in the A1_IN input properties. | |||
[[File:GPIO6_WaterMeter.png|thumb|center|800px| | [[File:GPIO6_WaterMeter.png|thumb|center|800px|Counter configuration interface view]] | ||
In the list of fields '''Pulse counter type (if any)''' choose the type '''water_meter'''. | |||
In the field '''Number of pulses per unit (kWh or m^3)''' specify how many pulses per cubic meter (for example, if 1 pulse of the counter corresponds to 10 liters, then specify 100; if 1 liter — 1000.) | |||
Field value '''Number of decimal places...''' specifies how many decimal places will be displayed in the Wiren Board interface. | |||
Save the settings by clicking the '''Save''' button at the top of the page and go to the list of devices on the '''Devices''' page. | |||
[[File:DiscreteIO.png|thumb|center|200px| | [[File:DiscreteIO.png|thumb|center|200px|Counter data]] | ||
Find the device '''Discrete I/O''' and see that it has new properties: "A1_IN_current" and "A1_IN_total". The field "A1_IN_current" shows the current water consumption, and "A1_IN_total" — what amount was spent from the moment of connection. In mqtt, these fields correspond to the topics '''/devices/wb-gpio/controls/A1_IN_current''' and '''/devices/wb-gpio/controls/A1_IN_total'''. | |||
Value '''A1_IN_total''' persists after restarting the controller (as retained in the message storage mqtt broker). |