WBE2-I-RS485-ISO RS485 Extension Module/en: различия между версиями
(Новая страница: «{| class="wikitable" !Terminal !Function |- |O1 |A (D+) |- |O2 |B (D-) |- |O3 |Isolated GND (Common, C) |}») |
(Новая страница: «==Configuration== Configuration is done in the web interface. Section Configs => Hardware Modules Configuration. Next, in Internal slot 1 or in Internal slot 2, s…») |
||
Строка 26: | Строка 26: | ||
|} | |} | ||
== | ==Configuration== | ||
Configuration is done in the web interface. Section Configs => Hardware Modules Configuration. | |||
Next, in Internal slot 1 or in Internal slot 2, select "WBE2-I-RS485-ISO: Isolated RS-485 interface module" and click Save. | |||
Версия 10:49, 27 июня 2019
Module with galvanically isolated RS-485 interface. Insulation voltage: 1.5 kV. Speed up to 1 Mbit/s.
Module contains 120 Ohm terminator between lines A and B. To enable it, close the jumper between termination contacts on the top edge of the board.
Pinout
RS485 signals are output to the terminals of the O1-O3 extension module.
Terminal | Function |
---|---|
O1 | A (D+) |
O2 | B (D-) |
O3 | Isolated GND (Common, C) |
Configuration
Configuration is done in the web interface. Section Configs => Hardware Modules Configuration. Next, in Internal slot 1 or in Internal slot 2, select "WBE2-I-RS485-ISO: Isolated RS-485 interface module" and click Save.
Устройство определяется сразу же, перезагрузка не требуется.
Работа
Порт доступен в системе как
- /dev/ttyMOD1 - при установке в первый модуль расширения (MOD1)
- /dev/ttyMOD2 - при установке во второй модуль расширения (MOD2)
Для работы необходимо отключить аппаратный контроль потока. Дополнительная конфигурация порта как RS-485 не требуется.