Purpose

The device is designed for tasks that require monitoring of currents and voltages in DC networks, for example for technical metering of electricity.

The device directly measures the voltage and current in the load. The values obtained are used to calculate power (kW) and energy (kWh).

Technical specifications

Contains 4 inputs for Hall sensors for load current measurement and 1 (2) input for voltage measurement.

Parameter Value
voltage measuring Inputs
Number of inputs 2 (single-ended)
1 (differential)
Input type voltage measurement,

uninsulated

Measured voltage 48V DC (0-70V)
Allowable voltage -70V ... +70V DC
Input impedance 10 kOhm
current measuring Inputs
Number of inputs 4
Input type connecting hall sensors
Sensor type open-loop,

5V power supply,

output 2.5 V +/- 0.625 V (FS)

Allowable voltage -5V .. +5V
Power output for hall sensors 5V, common to all sensors

with short circuit protection

Other
Module type "I" (inverted address scheme)
Maximum power consumption 0.1 W
Width, DIN units 2
Size 36,3x90,2x57,5 mm
Dimensions

Подключение к контроллеру

Смотрите раздел Активирование нового модуля в веб-интерфейсе контроллера


Подключение

WBIO-AI-DCM-4 Wiring