WB Dimmers Modbus Registers Map

Материал из Wiren Board
Версия от 20:11, 19 июля 2019; RomanKulibaba (обсуждение | вклад) (Новая страница: «| 0 ||holding||RW||-||0-255||Channel level G, logarithmic curve | |- |1||holding||RW||-||0-255||the Level of the R channel, the logarithmic curve | |- |2 |holding…»)

Другие языки:


Dimmers for LED strips support the following Modbus registers:

Register map

Register / address type read-write default format Purpose Note
0 holding RW - 0-255 Channel level G, logarithmic curve
1 holding RW - 0-255 the Level of the R channel, the logarithmic curve
2 holding RW - 0-255 Channel B Level, logarithmic curve
3 holding RW - 0-255 Level of the channel W, the logarithmic curve WB-MRGBW-D
5 holding RW 0 0: standard mode, 1: disable control button operation mode
6 input R 1 - pressed, 0 - released the state of the button 1
7 input R 1 - pressed, 0 - released button status 2
8 input R 1 - pressed, 0 - released button status 3 (WB-MRGBW-D)
9 holding RW 0 freq = 24 kHz / (value + 1) (0 - 239) PWM frequency
13 holding RW 100 x 10ms (2 - 500) Time for a smooth change of the brightness during turn on and off
32 input R number of button presses 1 since version 1.1.1
33 input R number of button presses 2 since version 1.1.1
34 input R number of button presses 3 since version 1.1.1
110 holding RW 96 baud rate / 100
( 24, 48, 96, 192, 384, 576, 1152 )
RS-485 port speed, "'divided by 100"'.
(configure RS-485 communication parameters for wiren Board modbus devices)
111 holding RW 0 0 - no parity bit (none), 1 - odd (odd), 2 - even (even) RS-485 port parity bit setting.
112 holding RW 2 1 or 2 number of stop bits of RS-485 port.
128 (0x80) holding RW 1 Modbus device address everything
129 (0x81) holding RW 0 0 or 1 Go to bootloader mode 1.2.0
200-206 input R {'W','B','M','R','G','B'}

0x0057 0x0042 0x004d 0x0052 0x0047 0x0042

сигнатура все
220-241 input R __date__ __time__ дата сборки прошивки все
270-271 holding R Серийный номер устройства WB-MRGBW-D