Register / address type read-write default format appointment In modification
8 holding RW 0 seconds timeout for safe mode -R
50 input R - raw_val * 16

unsigned

Raw averaged value with gas sensor ADC all
51 input R - R × 0.1 (Ohm)

unsigned

The resistance value of the measuring element of the gas sensor
52 input R R/R0 * 1000

unsigned

RS/Rs0 ratio (see register 60)
60 holding RW R × 10 (Ohm)

unsigned

The resistance value Rs0 of the measuring element of the gas sensor at 100ppm for the registers 52 and 61-62
61 holding RW R/R0 * 1000

unsigned

Threshold for Rs/Rs0 (the rising edge, the threshold is exceeded)
62 holding RW R/R0 * 1000

unsigned

Threshold for Rs/Rs0 (falling edge, falling below the threshold value)
110 holding RW 96 baud rate / 100 RS-485 port speed, "'divided by 100"'. Permissible speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
(configure RS-485 communication parameters for wiren Board modbus devices)
all
111 holding RW 0 all
112 holding RW 2 number of stop bits of RS-485 port. Valid values: 1, 2 all
120 (0x78) holding RW 0 0 write to the register causes a reboot of the MK stateless everything
121 (0x79) input R - mV current supply voltage of the module everything
128 (0x80) holding RW 1 Modbus device address everything
200-206 input R | | signature everything
220-241 input | | | _date__ _time__ firmware build date everything