Translations:WB-MAI11 Modbus Analog Inputs/6/en
±(0.1% + 0.003·Rw) for three-wire circuit |- ! colspan="2" |Control |- |Management interface |RS-485 |- |Interface isolation |Galvanically isolated from measuring circuits |- |Communication protocol |Modbus RTU, address is set by software, factory settings are indicated on the label |- |RS-485 interface parameters |Default speed of 9600 bps; data bits 8; parity N; stop bits 2. Interface parameters can be configured programmatically:
- Speed: 1200, 2400, 4800, 9600 (default), 19200, 38400, 57600, 115200 bit/s
(configure RS-485 communication parameters for Wiren Board Modbus devices) - Data: 8 bit
- Parity check: none (default), 1 - odd (odd), 2 - even (even)
- Stop bits: 1, 2 (default)
|- |Ready for operation after power supply |1 c |- ! colspan="2" |dimensions |- |Size |106.25 x 90.2 x 57.5 mm |- ! colspan="2" |operating Conditions |- |Air temperature |-40°C to +80°C |- |Relative humidity |up to 98%, without condensation |}