Translations:WB-MIO-Modbus-Registers/38/en
Register/ Address | Type | R/ W | Default value | Format | Description |
---|---|---|---|---|---|
110 | holding | RW | 96 (0x60) | baud rate / 100 | RS-485 port speed , divided by 100. Permissible speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 (Configuring RS-485 communication parameters for wiren Board Modbus devices) |
111 | holding | RW | 0 | Configure the RS-485 port parity bit. Valid values: 0 - no parity bit (none), 1 - odd (odd), 2 - even (even) | |
112 | holding | RW | 2 | Number of stop bits of RS-485 port. Valid values: 1, 2 | |
120 (0x78) | holding | RW | 0 | 0 or higher than 0 | Restart. Writing to the register causes the MC to restart without saving state |
121 (0x79) | input | R | - | mV | Input voltage |
128 (0x80) | holding | RW | 1 | Device Modbus-address | |
200-206 | input | R | {'x','x','x','x','x','x'} | Signature | |
220-241 | input | R | __date__ __time__ | Firmware build date | |
250-269 | input | R | null-terminated string | Firmware version | |
270-271 | input | R | 32-bit unsigned int | Unique identifier (S/N) | |
990 | holding | R | Output module number 1 connected (0 = not connected, 1 = 8 channel, 2 = 16 channel) | ||
991 | holding | R | Модуль выхода номер 2 подключен (0 = не подключен, 1 = 8 канальный, 2 = 16 канальный) | ||
992 | holding | R | Output module number 1 connected (0 = not connected, 1 = 8 channel, 2 = 16 channel) | ||
993 | holding | R | Input module number 4 connected (0 = not connected, 1 = 8 channel, 2 = 16 channel) | ||
994 | holding | R | Output module number 4 connected (0 = not connected, 1 = 8 channel, 2 = 16 channel) | ||
995 | holding | R | Input module number 3 connected (0 = not connected, 1 = 8 channel, 2 = 16 channel) | ||
996 | holding | R | Input module number 2 connected (0 = not connected, 1 = 8 channel, 2 = 16 channel) | ||
997 | holding | R | Input module number 1 connected (0 = not connected, 1 = 8 channel, 2 = 16 channel) | ||
1250 - 1265 | holding | R | 16 bit unsigned int | Registers of counter inputs module number 1 | |
2250 - 2265 | holding | R | 16 bit unsigned int | Registers of counter inputs module number 2 | |
3250 - 3265 | holding | R | 16 bit unsigned int | Registers of counter inputs module number 3 | |
4250 - 4265 | holding | R | 16 bit unsigned int | Registers of counter inputs module number 4 | |
10999 | holding | RW | 0 | 0 or higher than 0 | Configuration flag of counter inputs module number 1 |
11000 - 11005 | holding | RW | 16 bit unsigned int | Registers of counter inputs module number 1 | |
11499 | holding | RW | 0 | 0 or higher than 0 | Configuration flag of counter inputs module number 1 |
11500 - 11505 | holding | RW | 16 bit unsigned int | Registers of counter outputs module number 1 | |
11999 | holding | RW | 0 | 0 or higher than 0 | Configuration flag of counter inputs module number 2 |
12000 - 12005 | holding | RW | 16 bit unsigned int | Registers of counter inputs module number 2 | |
12499 | holding | RW | 0 | 0 or higher than 0 | Configuration flag of counter outputs module number 2 |
12500 - 12505 | holding | RW | 16 bit unsigned int | Registers of counter outputs module number 2 | |
12999 | holding | RW | 0 | 0 or higher than 0 | Configuration flag of counter inputs module number 3 |
13000 - 13005 | holding | RW | 16 bit unsigned int | Registers of counter inputs module number 3 | |
13499 | holding | RW | 0 | 0 or higher than 0 | Configuration flag of counter outputs module number 2 |
13500 - 13505 | holding | RW | 16 bit unsigned int | Registers of counter outputs module number 3 | |
13999 | holding | RW | 0 | 0 or higher than 0 | Configuration flag of counter inputs module number 4 |
14000 - 14005 | holding | RW | 16 bit unsigned int | Registers of counter inputs module number 4 | |
14499 | holding | RW | 0 | 0 or higher than 0 | Configuration flag of counter outputs module number 4 |
14500 - 14505 | holding | RW | 16 bit unsigned int | Registers of counter outputs module number 4 | |
20000 - 20017 | holding | R | 16 bit signed int multiplied by 100 | The voltage value registers of the ADC module 1 | |
20500 - 20517 | holding | RW | 0 | int in range of: 0 - 7 | Configuration registers of the ADC module 1 |
21000 - 21017 | holding | R | 16 bit signed int multiplied by 100 | The voltage value registers of the ADC module 2 | |
21500 - 21517 | holding | RW | 0 | int in range of: 0 - 7 | Configuration registers of the ADC module 2 |
22000 - 22017 | holding | R | 16 bit signed int multiplied by 100 | The voltage value registers of the ADC module 3 | |
22500 - 22517 | holding | RW | 0 | int in range of: 0 - 7 | Configuration registers of the ADC module 3 |
23000 - 23017 | holding | R | 16 bit signed int multiplied by 100 | The voltage value registers of the ADC module 4 | |
23500 - 23517 | holding | RW | 0 | int in range of: 0 - 7 | Configuration registers of the ADC module 4 |