|- |110 |holding |RW |96 |baud rate / 100 |RS-485 port speed, "'divided by 100"'. Permissible speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
(configure RS-485 communication parameters for Wiren Board Modbus devices) | rowspan="3" |>3.1.0 |- |111 |holding |RW |0 | |configure the RS-485 port parity bit. Valid values: 0 - no parity bit (none), 1 - odd (odd), 2 - even (even) |- |112 |holding |RW |2 | |number of stop bits of RS-485 port. Valid values: 1, 2 |- | | | | | | | |- |120 (0x78) |holding |RW |0 |other than 0 |write to the register causes a reset of the module without saving state | |- |121 (0x79) |input |R | - |mV |current supply voltage of the module | |- |128 (0x80) |holding |RW |1 | |The Modbus address of the device | |- | 129 (0x81) || holding || RW|| 0 || 0 or 1 || Switch to bootloader mode || starting with firmware 4.5.0 |- |200-206 |input |R |see device Signature | |signature | |- |220-241 |input |R | |__date__ _ _ time__ |the build date of the firmware | |- |245 |holding |RW |216 |°C × 100 (signed) |Self-heating compensation of the built-in temperature sensor. The register value is subtracted from the temperature measured by the built-in sensor (register 6) | |- |250-269 |input |R | |string, null-terminated |firmware version | |- |270-271 |input |R | |32-bit unsigned int |unique identifier (S/N) | |- | | | | | | | |- |275 |holding |RW |0 |0 or 1 |1-W input mode: 0 - 1-wire, 1 - discrete input | rowspan="3" |>=4.0.0 |- |277 |input |R | |16-bit unsigned int |Counter for 1-W input |- |0 |discrete |R | |0 or 1 |Current state of input 1-W: 0 - open, 1 - GND closed. If 1-wire mode is selected for input, the value is always 0. |- |16 |discrete |R | |0 or 1 |Sensor polling status 1-Wire input no. 1: 0 - sensor not connected, 1 - sensor connected and correctly polled |starting with firmware v.4.6.0 |}