Register/ address | type | read-write | default | format | appointment |
---|---|---|---|---|---|
6 | input | R | 0x7FFF — sensor not connected or defective | °C × 16 (signed) | Temperature from external sensor |
7 | input | R | 0x7FFF — sensor is not connected or defective | °C × 16 (signed) | Temperature from external sensor |
110 | holding | RW | 96 (0x60) | baud rate / 100 | RS-485 port speed, "'divided by 100"'. Permissible speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 (configure RS-485 communication parameters for wiren Board modbus devices) |
111 | holding | RW | 0 | configure the RS-485 port parity bit. Valid values: 0 - no parity bit (none), 1 - odd (odd), 2 - even (even) | |
112 | holding | RW | 2 | number of stop bits of RS-485 port. Valid values: 1, 2 | |
120 (0x78) | holding | RW | 0 | non-0 | writing to the register causes the module to restart without saving state |
121 (0x79) | input | R | - | mV | current supply voltage of the module |
128 (0x80) | holding | RW | 1 | Modbus device address | |
200-206 | input | R | | | signature | ||
220-241 | input | | | | _date__ _time__ | firmware build date | ||
250-269 | input | | | / string, null-terminated | firmware version | ||
270-271 | input | R | 32-bit unsigned int | unique identifier (S/N) | |
2000-2509 | holding | RW | IR transceiver period Buffer (2000-2201 in WB-MIR firmware versions up to 4.1.0) |