Translations:WBIO-AI-DV-12 Analog Inputs/123/en

Материал из Wiren Board

The WBIO-AI-DV-12 module can also be connected via the interface Converter WB-MIO. Two device templates can be used: WBIO-AI-DV-12-50V and WBIO-AI-DV-12. If they are not in the Configurator, you need to update wb-mqtt-serial with apt-get update && apt-get install wb-mqtt-serial. The WBIO-AI-DV-12-50V template is designed for devices where jumpers are installed (voltage measurement on differential inputs in the range from 0 to 50 V), and the WBIO-AI-DV-12 template is for devices with removed jumpers (voltage measurement on differential inputs from 0 to 400 mV, on unipolar — from 0 to 2.5 V).