WBIO-DO-R10R-4: 10A relay outputs and roller shutter module

Материал из Wiren Board
Это утверждённая версия страницы. Она же — наиболее свежая версия.
Другие языки:

Buy online

WBIO-DO-R10R-4

Purpose

Control of electric curtains, shutters, shutoff valves.

Technical specifications

Contains 4 relay groups.


Each group has three possible states.

Parameter Value
Number of output groups 4
Output type mechanical relay
Contact configuration SPCO/all sptt (see scheme)

output group states:

  • off,
  • LX and NC closed,
  • Lx and NO closed
Maximum switching voltage, AC 250 V
Maximum switching voltage, DC 30 Volts
Maximum switching current, per channel (*) 3 A
The channel resistance in the open state < 100 mOhm
Voltage isolation between the controller and the output 1500 V (RMS.)
Lifetime: number of switches

for 10 A 230 V AC load, cos φ = 1

100 000
Module type "O" (non-inverted address scheme)
Maximum power consumption 1 W
Width, DIN units 3
Size 53,3x90,2x57,5 mm

*) Maximum switching current is specified for 230 VAC resistive load.


Terminals and wire section
The recommended wire cross section with pin bushing insulated tip, mm2 2,5
Standard sleeve length of pin bushing insulated tip, mm 8
Tightening torque of screws, Н∙м 0,5
Dimensions

Connection to the controller

Connection to the controller

See Activating the modules in the web interface of the controller. In the Discrete I/O device, EXT(1-8)_DIR(1-4) and EXT(1-8)_ON(1-4) controls will be created after the module connection. DIR controls are responsible for direction selection (relay R2 on the circuit), and ON controls are responsible for switching on and off (relay R1 on the circuit). These controls in MQTT messages are called /devices/wb-gpio/controls/EXTx_DIRy and /devices/wb-gpio/controls/EXTx_ONy.

Module's controls in the web interface

Module outputs — load connection

The phase wire is connected to the Lx terminals. Both terminals of the Lx contact group are connected on the board. NC and NO terminals are connected to the engine, setting the direction of rotation. The NO and NC outputs are protected by varistors.

Wiring diagram of the engine to the WBIO-DO-R10R-4 module

Images and drawings of the device


По ссылкам ниже вы можете скачать изображения и чертежи устройства WBIO-DO-R10R-4.

Corel Draw 2018: WBIO-DO-R10R-4.cdr.zip

Corel Draw PDF: WBIO-DO-R10R-4.cdr.pdf

Autocad 2013 DXF: WBIO-DO-R10R-4.dxf.zip

Autocad PDF: WBIO-DO-R10R-4.pdf