Wbincludes:WB-REF-U Carel BASIC Modbus Registers

Материал из Wiren Board
Адрес Тип Формат Имя Назначение Единицы
измерения
Значения
в Hex в DEC Минимум Максимум
0x0004 4 discrete bool s_pre1 1st probe alarm
0x0001 1 discrete bool s_pre2 2nd probe alarm
0x0009 9 discrete bool s_pre3 3rd probe alarm
0x000C 12 discrete bool s_LO Low temperature alarm
0x0003 3 discrete bool s_HI High temperature alarm
0x0006 6 discrete bool s_IA External immediate alarm
0x000F 15 discrete bool s_dA External delay alarm
0x000A 10 discrete bool s_Ed1 Timeout defrost alarm
0x000E 14 discrete bool s_cht High temperature condense
0x0002 2 discrete bool s_CHT High temperature condense
0x0005 5 discrete bool s_Etc Broken RTC alarm
0x0017 23 discrete bool s_EE Machine parameters eeprom
0x0010 16 discrete bool s_EF Functions parameters eepr
0x0019 25 discrete bool s_PreDor Pre-opened door alarm 0 0
0x001C 28 discrete bool s_Dor Opened door alarm 0 0
0x0195 405 input s16 s_pr1 Probe 1 reading 0.1°C/°F 0 0
0x0199 409 input s16 s_pr2 Probe 2 reading 0.1°C/°F 0 0
0x0196 406 input s16 s_pr3 Probe 3 reading 0.1°C/°F 0 0
0x0193 403 holdng s16 /C1 Probe 1 offset 0.1°C/°F -20 20
0x019C 412 holdng s16 /C2 Probe 2 offset 0.1°C/°F -20 20
0x019A 410 holdng s16 St Set point 0.1°C/°F
0x019E 414 holdng s16 rd Control differential 0.1°C/°F 0 19
0x019F 415 holdng s16 r1 Minimum set point allowe 0.1°C/°F -50
0x0197 407 holdng s16 r2 Maximum set point allowed 0.1°C/°F 90
0x019B 411 holdng s16 dt End defrost temperature 0.1°C/°F -50 90
0x019D 413 holdng s16 A0 Alarm and fan differentia 0.1°C/°F -20 20
0x0190 400 holdng s16 AL Absolute/Relative tempera 0.1°C/°F -50 90
0x0198 408 holdng s16 AH Absolute/Relative tempera 0.1°C/°F -50 90
0x0192 402 holdng s16 F1 Fan control set point 0.1°C/°F -50 90
0x0007 7 discrete u16 s_din1 Status of digital input 1 0 0
0x0000 0 discrete u16 s_r1 Compressor relay status 0 0
0x000D 13 discrete u16 s_r2 Defrost relay status 0 0
0x0008 8 discrete u16 s_r3 Fan relay status 0 0
0x000B 11 discrete u16 s_r4 Auxiliary relay status 0 0
0x001D 29 discrete u16 s_DEF Defrost status 0 0
0x0018 24 coil s16 s_cDEF Defrost command 0 1
0x001B 27 discrete u16 s_CC Continuous cycle status 0 0
0x0014 20 coil u16 s_cCC Continuous cycle command 0 1
0x0013 19 coil u16 F0 Fan management 0 1
0x0016 22 coil u16 F3 Fan in defrost 0 1
0x001F 31 coil u16 s_cONOFF ON/OFF command 0 1
0x01A6 422 holdng u16 c0 Comp. and fan start delay Минуты 0 99
0x01A3 419 holdng u16 c2 Minimum compressor off ti Минуты 0 99
0x01AC 428 holdng u16 d0 Defrost type 0 4
0x01AA 426 holdng u16 dI Interval between defrosts Часы 0 24
0x01AE 430 holdng u16 dP Maximum defrost duration Минуты 1 99
0x01AF 431 holdng u16 dd Dripping time after defro Минуты 0 15
0x01A7 423 holdng u16 Ad Low and high temperature Минуты 0 99
0x01AB 427 holdng u16 A4 Third input configuration 0 2
0x01AD 429 holdng u16 F2 Fan off with compressor o 0.1°C/°F 0 2
0x01A0 416 holdng u16 Fd Post dripping time Минуты 0 15
0x01A8 424 holdng u16 F4 Start delay when fan on Секунды 1 99
0x01A2 418 holdng u16 F5 Fan on time (with F2=2) Минуты 1 99
0x01A1 417 holdng u16 F6 Fan off time (with F2=2) Минуты 1 99
0x01A4 420 input s16 H0 Serial address 0 207