WB-MRWL3 Modbus Relay Modules/en: различия между версиями
FuzzyBot (обсуждение | вклад) (Часть переводимой страницы WB-MRWL3 Modbus Relay Module.) |
(Новая страница: «All connections are realized by blocks of screw clips. The wire section for contacts K1 — K3 must correspond to the switched load.») |
||
(не показано 14 промежуточных версий 2 участников) | |||
Строка 69: | Строка 69: | ||
The inputs have two modes of operation: trigger mode (for control with buttons) and repeat mode (for control with switches). In the trigger mode, to change the state of the relay, it is enough to close and open the input once. The change of state occurs on the rising edge ( | The inputs have two modes of operation: trigger mode (for control with buttons) and repeat mode (for control with switches). In the trigger mode, to change the state of the relay, it is enough to close and open the input once. The change of state occurs on the rising edge (when the circuit is closed). In the repeat mode, the relay state is determined by the input state: the input is closed — the relay is on, open — off. Details about the mode switching written in [[ Modbus Management Of Relay Modules/en|Modbus Management Of Relay Modules]]. | ||
Строка 204: | Строка 204: | ||
All connections are realized by blocks of screw clips. The wire section for contacts K1 — K3 must correspond to the switched load. | All connections are realized by blocks of screw clips. The wire section for contacts K1 — K3 must correspond to the switched load. | ||
При подключении коммутируемых устройств к контактам реле K1 — K3 важно не превышать рекомендованный ток — 20 А. | |||
Ток, протекающий при замыкании кнопки или выключателя, невелик, так что тип кнопки или выключателя может быть любым. Несмотря на встроенную защиту от дребезга, выбирайте качественные кнопки и выключатели, чтобы исключить ложные срабатывания из-за плохих контактов. | |||
Если устройство — последнее на линии RS-485, то между его входами A и B необходимо установить резистор-терминатор сопротивлением 120 Ом. Практика показывает, что в случае стендовых испытаний при небольшой длине линии RS-485 и небольшом количестве устройств терминатор на последнем устройстве в линии можно не устанавливать. | |||
Модуль необходимо устанавливать таким образом, чтобы удовлетворять требованиям электробезопасности и не допускать случайного касания контактов, находящихся под высоким напряжением. Модуль должен эксплуатироваться при рекомендованных условиях окружающей среды. | |||
<!--[[File:Installation_WB3_+_WB5_+_DIN.png|850px|thumb|center|Образец монтажа и подключения модуля WB-MR3HV/I. Выбор качественного блока питания очень важен для работы модуля. Кнопка с проводами желтого цвета, подключенная ко входу "4" модуля, отключает все три канала одновременно.]]--> | <!--[[File:Installation_WB3_+_WB5_+_DIN.png|850px|thumb|center|Образец монтажа и подключения модуля WB-MR3HV/I. Выбор качественного блока питания очень важен для работы модуля. Кнопка с проводами желтого цвета, подключенная ко входу "4" модуля, отключает все три канала одновременно.]]--> | ||
== | == Режим работы реле в случае отключении питания == | ||
В зависимости от значения, записанного в регистр хранения 0x06, после отключения и восстановления питания модуля реле останутся выключенными (если значение — 0, или включатся те, которые были включены до перерыва в питании, если в регистре записано значение 1). | |||
==Modbus | == Управление по Modbus == | ||
Подробно о работе с модулем по протоколу Modbus написано в разделе [[Relay Module Modbus Management|Управление модулями реле Wirenboard по протоколу Modbus]]. | |||
Там же можно найти карту регистров устройства. | |||
[[Периферийные устройства с интерфейсом RS-485 серии WB-xxxx | [[Периферийные устройства с интерфейсом RS-485 серии WB-xxxx |Назад к списку периферийных устройств]] | ||
== | == Обновление прошивки устройства == | ||
Начиная с новых версий микропрограмм устройства поддерживается функционал обновления прошивки (микропрограммы) по протоколу Modbus. Это дает возможность расширять функциональные возможности устройств и устранять ошибки в микропрограммном обеспечении непосредственно на месте монтажа. Подробнее о перепрошивке устройств рассказано в статье [[WB-MCU-Flasher|Загрузка прошивок на устройства Wiren Board]]. Список версий прошивок, поддерживающих обновление, а также устройств, для которых эта функция реализована, можно найти в статье [[Firmware_Changelog]]. | |||
== | == Известные неисправности == | ||
[[WB-MR:_Errata | [[WB-MR:_Errata |Список известных неисправностей]] | ||
== | == Изображения и чертежи устройства == | ||
{{Wbincludes:WBPictures|1}} | {{Wbincludes:WBPictures|1}} |
Версия 19:28, 18 июля 2019
Three-channel relay modules WB-MRWL3 are used in industrial and home automation systems. They are intended for commutation of powerful power load of General purpose, including inductive: control of groups of sockets, engines, heaters, etc.
WB-MRWL3 modules are designed for rated load up to 20A (4.5 kW) per channel and can be used directly without intermediate contactors for switching outlet groups and other loads protected by an automatic switch with a nominal value of 16A.
WB-MRWL3 hass an input that simultaneously deactivates all the load.
Outputs
The module has three independent normally-open relay outputs.
Relays are certified only for use on alternating current, the load capacity of the DC may be lower. Each relay contact is protected from arcing when the varistor closes/opens. Depending on the Modbus register settings, the state of the inputs can be resumed after a power interruption (see #Relay operation mode in case of power loss). The table below lists the technical characteristics of the relays used in the module.
Relay parameters
Our detailed article in Russian on habr.com about the choice of relay parameters for the switched load: https://habr.com/ru/company/wirenboard/blog/422197/
Maximum switching current,
resistive load 230V AC |
20A |
Maximum allowable inrush current
(within 20ms, for no contact) |
30A |
Contact resistance | < 100 milliohms |
Contact material | AgSnO2 |
Contact configuration | SPST (NO, COM) |
Lifetime: number of switches
for load 20A 230V AC, cos φ = 1 |
30 000 |
Lifetime: number of switches
without load |
1 000 000 |
Relay model | Hongfa HF161F-W |
Peculiar properties | High current |
Application | General purpose power load, inductive load. |
Inputs
The inputs of the WB-MRWL3 modules are led out on detachable screw terminals. Inputs are organized on the dry contact principle. Buttons or switches are connected between the corresponding inputs and iGND inputs.
The 3 inputs can be used for direct control of the respective relay channels. Another input can be used for group disconnection of all channels.
The inputs have two modes of operation: trigger mode (for control with buttons) and repeat mode (for control with switches). In the trigger mode, to change the state of the relay, it is enough to close and open the input once. The change of state occurs on the rising edge (when the circuit is closed). In the repeat mode, the relay state is determined by the input state: the input is closed — the relay is on, open — off. Details about the mode switching written in Modbus Management Of Relay Modules.
IMPORTANT: it is not recommended to use switches (lock buttons) in the trigger mode of inputs. Input interference may be perceived as a short release/push of the button and the relay status will change, although the switch will remain closed.
Technical specifications
Parameter | Value |
---|---|
Power | |
Supply voltage | 12 — 28 V DC |
Power consumption |
|
Terminals and wire section | |
Recommended wire cross-section with NSUI, mm2 | 0,75 — 1 for control inputs, 2 x 2.5 for relay outputs |
Length of the standard sleeve NSVE, mm | 8 (10 for relay outputs) |
Torque of screws, N∙m | 0,2 for control inputs , 0,4 — for power outputs |
Outputs | |
Output type | Mechanical relay contacts |
Output configuration | 3 / output connected to the relay contacts |
Configuration of each output contacts | Two-position, normally open (S and NO) |
Maximum switching voltage, AC | 250 V |
Maximum switching voltage, DC | 30 Volts |
Rated current per channel | 20 A |
Contact resistance | < 100 milliohms |
Voltage isolation between the controller and the output | 1500 V (RMS value) |
Term life: | see table in #Relay parameters |
Inputs | |
Number of inputs (Inputs 0—3) | 4 (3+1) |
Input type | "Dry contact", group insulation.
The input voltage is ~4.5 V. Current closing input ~2mA. |
Functions |
|
Control | |
Management interface | RS-485 |
Interface isolation | Uninsulated |
Communication protocol | Modbus RTU, the address is set by software, factory settings are indicated on the label |
RS-485 interface parameters | set programmatically (see register card); default: speed — 9600 bit/s; data — 8 bit; parity bit — none (N); stop bits — 2 |
Ready for operation after power supply | ~0.03 c |
dimensions | |
Width, DIN units | 3 |
Overall dimensions (l x W x h) | 53.3 x 90.2 x 57.5 mm |
Display | |
Power and data exchange indication | Green status led |
Relay channel status indication | Red LEDs, 1 — 3 |
Operating conditions | |
Air temperature | |
Relative humidity | Up to 85%, without condensation |
Габаритные размеры модулей
Installation of modules
The relay module is mounted on a standard 35 mm wide DIN rail and occupies a width of 3 DIN modules.
All connections are realized by blocks of screw clips. The wire section for contacts K1 — K3 must correspond to the switched load.
При подключении коммутируемых устройств к контактам реле K1 — K3 важно не превышать рекомендованный ток — 20 А.
Ток, протекающий при замыкании кнопки или выключателя, невелик, так что тип кнопки или выключателя может быть любым. Несмотря на встроенную защиту от дребезга, выбирайте качественные кнопки и выключатели, чтобы исключить ложные срабатывания из-за плохих контактов.
Если устройство — последнее на линии RS-485, то между его входами A и B необходимо установить резистор-терминатор сопротивлением 120 Ом. Практика показывает, что в случае стендовых испытаний при небольшой длине линии RS-485 и небольшом количестве устройств терминатор на последнем устройстве в линии можно не устанавливать.
Модуль необходимо устанавливать таким образом, чтобы удовлетворять требованиям электробезопасности и не допускать случайного касания контактов, находящихся под высоким напряжением. Модуль должен эксплуатироваться при рекомендованных условиях окружающей среды.
Режим работы реле в случае отключении питания
В зависимости от значения, записанного в регистр хранения 0x06, после отключения и восстановления питания модуля реле останутся выключенными (если значение — 0, или включатся те, которые были включены до перерыва в питании, если в регистре записано значение 1).
Управление по Modbus
Подробно о работе с модулем по протоколу Modbus написано в разделе Управление модулями реле Wirenboard по протоколу Modbus. Там же можно найти карту регистров устройства.
Назад к списку периферийных устройств
Обновление прошивки устройства
Начиная с новых версий микропрограмм устройства поддерживается функционал обновления прошивки (микропрограммы) по протоколу Modbus. Это дает возможность расширять функциональные возможности устройств и устранять ошибки в микропрограммном обеспечении непосредственно на месте монтажа. Подробнее о перепрошивке устройств рассказано в статье Загрузка прошивок на устройства Wiren Board. Список версий прошивок, поддерживающих обновление, а также устройств, для которых эта функция реализована, можно найти в статье Firmware_Changelog.
Известные неисправности
Список известных неисправностей
Изображения и чертежи устройства
По ссылкам ниже вы можете скачать изображения и чертежи устройства WB-MRWL3.
Corel Draw 2018: WB-MRWL3.cdr.zip
Corel Draw PDF: WB-MRWL3.cdr.pdf
Autocad 2013 DXF: WB-MRWL3.dxf.zip
Autocad PDF: WB-MRWL3.pdf