Translations:WB Dimmers Modbus Registers Map/5/en: различия между версиями
(Новая страница: «| 0 ||holding||RW||-||0-255||Channel level G, logarithmic curve | |- |1||holding||RW||-||0-255||the Level of the R channel, the logarithmic curve | |- |2 |holding…») |
(нет различий)
|
Версия 20:11, 19 июля 2019
| 0 ||holding||RW||-||0-255||Channel level G, logarithmic curve
|
|-
|1||holding||RW||-||0-255||the Level of the R channel, the logarithmic curve
|
|-
|2
|holding
|RW
|-
|0-255
|Channel B Level, logarithmic curve
|
|-
|3
|holding
|RW
|-
|0-255
|Level of the channel W, the logarithmic curve
|WB-MRGBW-D
|-
|
|
|
|
|
|
|
|-
|5
|holding
|RW
|0
|0: standard mode, 1: disable control
|button operation mode
|
|-
|6
|input
|R
|
|1 - pressed, 0 - released
|the state of the button 1
|
|-
|7
|input
|R
|
|1 - pressed, 0 - released
|button status 2
|
|-
|8
|input
|R
|
|1 - pressed, 0 - released
|button status 3 (WB-MRGBW-D)
|
|-
|9
|holding
|RW
|0
|freq = 24 kHz / (value + 1) (0 - 239)
|PWM frequency
|
|-
|13
|holding
|RW
|100
|x 10ms (2 - 500)
|Time for a smooth change of the brightness during turn on and off
|
|-
|||||||||||
|
|-
|32
|input
|R
|
|
|number of button presses 1
|since version 1.1.1
|-
|33
|input
|R
|
|
|number of button presses 2
|since version 1.1.1
|-
|34
|input
|R
|
|
|number of button presses 3
|since version 1.1.1
|-
| 110 || holding || RW|| 96 || baud rate / 100
( 24, 48, 96, 192, 384, 576, 1152 )|| RS-485 port speed, "'divided by 100"'.
(configure RS-485 communication parameters for wiren Board modbus devices)
|
|-
| 111 || holding || RW|| 0 || 0 - no parity bit (none), 1 - odd (odd), 2 - even (even) || RS-485 port parity bit setting.
|
|-
| 112 || holding || RW|| 2 || 1 or 2 || number of stop bits of RS-485 port.
|
|-
| 128 (0x80) || holding || RW|| 1 || || Modbus device address
|everything
|-
| 129 (0x81) || holding || RW|| 0 || 0 or 1 || Go to bootloader mode
|1.2.0
|-
| 200-206 || input || R ||{'W','B','M','R','G','B'}